Catalogue

106 RLC-PRC029-EN
Electrical Data
Table 54. Customer Wire Selection – RTWD – 50 Hz – standard efficiency – standard condensing temperature
Wire Selection
Main Terminal Block
Wire Selection
Non-Fused Disconnect
Wire Selection
Circuit Breaker
Unit
ID
Rated
Voltage
#
Conn
Size
amps
XL Wire
Range
YD Wire
Range
Size
amps
XL Wire
Range
YD Wire
Range
Size
amps
XL Wire
Range
YD Wire
Range
RTWD
70
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 150 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 100 #6–#350 #6–#350
RTWD
80
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 175 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0
100
125
#6–#350 #6–#350
RTWD
90
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 175 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 125 #6–#350 #6–#350
RTWD
100
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 200 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0
125
150
#6–#350 #6–#350
RTWD
110
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 225 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 150 #6–#350 #6–#350
RTWD
120
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 250 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0
150
175
#6–#350 #6–#350
RTWD
130
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 250 #6–#350 #6–#350
400/50/3 2 195 #14–2/0 #14–2/0 100 #10–1/0 #10–1/0 175 #6–#350 #6–#350
RTWD
140
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 300 3/0-(2)500 3/0-(2)500
400/50/3 2 195 #14–2/0 #14–2/0
100
250
#10–1/0
#6–#350
#10–1/0
#6–#350
175
200
#6–#350 #6–#350
RTWD
150
400/50/3 1 380 #4–500 #4–500 250 #6–#350 #6–#350 300 3/0-(2)500 3/0-(2)500
400/50/3 2 195 #14–2/0 #14–2/0 250 #6–#350 #6–#350 200 #6–#350 #6–#350
1. Optional non-fused disconnect and circuit breaker.
2. Copper wire only, based on nameplate minimum circuit ampacity (MCA).
3. Standard condensing temperature option refers to entering condenser water temperatures 95°F (35°C) and below.
4. Circuit two information is the same as circuit one unless listed on a separate line below circuit one values.
5. XL - across-the-line starter and YD - wye-delta starter.