Catalogue
46 CG-PRC017H-EN
Dimensions
Figure 8. CGAM 40 and 52 ton — no options
Control Panel
Wire
Connection
84.8 in
(2155 mm)
Fan Compressor
Chilled water
inlet
Chilled water
outlet
88.4 in
(2245 mm)
113.8 in (2890 mm)
23.8 in
(603 mm)
89.9 in(2282 mm)
14.4 in
(367 mm)
7. 9 i n
25.8 in
Water connections are even with unit end.
(656 mm)
(200 mm)
The number of fans shown does not represent the number of fans installed.
Figure 9. CGAM 40 and 52 ton- service clearances and mounting locations
Mounting Locations
Door
Service Clearance
Hole dia
Distance from edge to
(1000 mm)
39.4 in
(1000 mm)
(493 mm)
39.4 in
94 in (2388 mm)
47.2 in
(1200 mm)
85.4 in
Swing
19.4 in
0.56 in (15 mm)
middle of mounting hole
(2164 mm)
1.5 in (38 mm)
31.5 in
(800 mm)
Control
panel side
Total of four mounting locations.More clearance may be needed for airflow
depending on the installation.
Chilled water
connection side
The number of fans shown does not represent the number of fans installed.