Specification Sheet
22-1921-1C-EN
9
MODEL
S9V2D120U5PSBA
(a)
S9V2B040D3PSBA
(a)
S9V2B060D3PSBA
(a)
S9V2B080D3PSBA
(a)
Drive — No. Speeds
Direct - 2 Direct - 2 Direct - 2 Direct - 2
Motor HP — RPM
3300/2600 3300/2600 3300/2600 3300/2600
Volts/Ph/Hz 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
FLA 0.66 0.66 0.66 0.66
FILTER — Furnished? No No No No
Type recommended High Velocity High Velocity High Velocity High Velocity
Hi Vel. (No.-Size-Thk.)
1 — 24x25 — 1 in. 2 — 14x20 — 1 in. 2 — 14x20 — 1 in. 2 — 14x20 — 1 in.
VENT PIPE DIAMETER — Min (in.)
(e) (f)
3 Round 2 Round 2 Round 2 Round
HEAT EXCHANGER
Type — Fired
409 Stainless Steel 409 Stainless Steel 409 Stainless Steel 409 Stainless Steel
— Unfired 29–4C Stainless Steel 29–4C Stainless Steel 29–4C Stainless Steel 29–4C Stainless Steel
Gauge (Fired)
20 20 20 20
ORIFICES — Main
Nat. Gas Qty. — Drill Size
6 - 45 2- 45 3 - 45 4 - 45
LP Gas Qty. — Drill Size
6- 56 2- 56 3 - 56 4 - 56
GAS VALVE
Redundant - Two Stage Redundant - Two Stage Redundant - Two Stage Redundant - Two Stage
PILOT SAFETY DEVICE
Type 120 V SiNi Igniter 120 V SiNi Igniter 120 V SiNi Igniter 120 V SiNi Igniter
BURNERS — Type Multiport Inshot Multiport Inshot Multiport Inshot Multiport Inshot
Number 6 2 3 4
POWER CONN. — V/Ph/Hz
(g)
120 / 1 / 60 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
Ampacity (In Amps)
13.9 7.9 7.9 7.9
Max. Overcurrent Protection (Amps)
15 15 15 15
PIPE CONN. SIZE (in.)
1/2 1/2 1/2 1/2
DIMENSIONS H x W x D H x W x D H x W x D H x W x D
Uncrated (In.)
34 x 24-1/2 x 28–3/4 34 x 17-1/2 x 28–3/4 34 x 17-1/2 x 28–3/4 34 x 17-1/2 x 28–3/4
Crated (In.)
35-1/2 x 26-1/2 x 30-7/8 35-1/2 x 19-1/2 x 30-7/8 35-1/2 x 19-1/2 x 30-7/8 35-1/2 x 19-1/2 x 30-7/8
WEIGHT
Shipping (Lbs.)/Net (Lbs.)
167/156 122/114 127/119 132/124
(a)
Meets Energy Star
(b)
For U.S. applications, above input ratings (BTUH) are up to 2,000 feet, derate 4% per 1,000 feet for elevations above 2,000 feet above sea level. For
Canadian applications, above input ratings (BTUH) are up to 4,500 feet, derate 4% per 1,000 feet for elevations above 4,500 feet above sea level.
(c)
Central Furnace heating designs are certified to ANSI Z21.47 / CSA 2.3.
(d)
Based on U.S. government standard tests.
(e)
Refer to the Vent Length Table in the Installer's Guide.
(f)
All S9V2 furnace models have a vent outlet diameter that equals 2 in.
(g)
The above wiring specifications are in accordance with National Electrical Code; however, installations must comply with local codes.
PPrroodduucctt SSppeecciiffiiccaattiioonn