Programming Guide

DIAGNOSTICS Menu
46 PKG-SVP01D-EN
Active Diagnostic -- Manual Reset
Used With: All units
Factory Presets: N/A
___________________ More
Possible Values:
Low Pressure Control Open - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Manual Reset SA Static Pressure Limit
Compressor Contactor Fail - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Low Air Temperature Limit Trip
Compressor Trip - Ckt 1, Ckt 2, Ckt 3, Ckt 4 Emergency Stop
Note: The word “MORE” will appear on the screen if more than one failure has occurred.
OR
Active Diagnostic -- Auto Reset
___________________ More
Possible Values:
RTM Zone Heat Aux Temp
Supply Air Temp Unocc Zone Cool Setpoint
RTM Aux. Temp Unocc Zone Heat Setpoint
OA Temp Supply Air Pres Setpt
Mode Input Space Pressure Pres Setpt
Occ Zone Cool Setpoint Space Pressure
Occ Zone Heat Setpoint Return Air Temp
Supply Air Pres RA Humidity
OA Humidity
Auto Reset SA Static Pres
Limit
SCM Communication Evap Temp - CKT 1, 2, 3, 4
MCM Communication Heat Module Commun.
ECEM Communication Cond Temp - CKT 1, 2, 3, 4
TCI Communication
GBAS Module
Communication
Tracer® Communication NSB Panel Communication
Unit HI Communcation VOM Communication
Sup Air Temp Cool Setpt Sup Air Temp Heat Setpt
NSB Panel Zone Temp CO
2
Sensor
VCM Aux Temp Velocity Press
VCM Communication WSM Communication
Ent Cond Water Temp Ent Water Temp
WSM Mixe Air Temp Water Flow
OR
1. Pressing the "NEXT" key to view the diagnostics will prompt the following screen if a "information only" failure has occurred.
Active Diagnostic -- Info
___________________ More
Possible Values:
Heat Fail
Dirty Filter
Ventilation Override Mode A, B, C, D, or E
RTM Data Storage Error
Note: Activation of any VOM mode can be viewed within the “Active Diagnostic” screen.