Programming Guide
Programming SETUP
34 PKG-SVP01D-EN
Actuator Setup Hydronic
Used With: All Units when Hydronic Heat is
installed.
Factory Presets: 150 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 150 Sec
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic
Used With: All Units when Hydronic Heat is
installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC
Min Voltage 2.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic
Used With: All Units when Hydronic Heat is
installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC
Max Voltage 10.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Hydronic
Used With: All Units when Hydronic Heat is
installed.
Factory Presets: DIRECT ACTING
Possible Values: DIRECT ACTING, REVERSE
ACTING
Direct/Reverse Act DIRECT ACTING
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 1 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 60 Sec
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 1 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC
Min Voltage 2.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 1 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC
Max Voltage 10.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 1 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
Direct/Reverse Act DIRECT ACTING
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 2 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 60 Seconds
Possible Values: 1 - 255 Seconds
Max Stroke Time 60 Sec
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 2 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 2.0 VDC
Possible Values: 0.0 to 9.9 Volts DC
Min Voltage 2.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 2 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: 10.0 VDC
Possible Values: 0.1 to 10.0 Volts DC
Max Voltage 10.0 VDC
1. Press the NEXT key until the following screen is displayed.
Actuator Setup Num 2 Low Ambient
Used With: Air-cooled units low ambient
damper installed.
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
Direct/Reverse Act DIRECT ACTING
1. Press the NEXT key until the following screen is displayed.