Programming Guide

General Information
12 PKG-SVP01D-EN
Default Setpoint Setups
Daytime warmup - initiate 67 °F p. 36
Daytime warmup - terminate 71 °F p. 36
Low ambient compressor lockout (std. units) 50 °F p. 38
Supply air temp - cooling 55 °F p. 36
Supply air temp - heating 100 °F p. 36
Unoccupied zone time - cool 85 °F p. 36
Unoccupied zone temp - heat 60 °F p. 37
Unoccupied zone temp - MWU 72 °F p. 37
Function (Enable/Disable) Setups
Compressor lead/lag Disable p. 23
Daytime warmup Disable p. 22
Morning warmup Enable p. 23
Supply air tempering Disable p. 23
Unoccupied economizer Enable p. 25
Unoccupied heating Enable p. 23
Unoccupied mechanical cooling Enable p. 23
Module Defaults
GBAS input/output assignments
GBAS input/output not assigned p. 29
Information format
Text displays
Unit displays
English
English
p. 22
p. 22
Reference Enthalpy
25 btu/lb. p. 37
RTM alarm output assignments
any active diagnostic p. 30
Sensor source selection for:
Daytime warmup RTM zone temp p. 27
Monitor Specified Temp. Input RTM zone temp p. 27
Morning warmup RTM zone temp p. 27
Unoccupied zone control RTM zone temp p. 27
Zone reset RTM aux temp p. 27
Setpoint source selection for:
Cooling supply air temp default p. 38
Heating supply air temp default p. 38
Morning warmup default p. 38
Unoccupied zone cooling default p. 38
Unoccupied zone heating default p. 38
Actuator setup:
Direct/reverse action direct acting p. 32 - p. 35
Max stroke time 150 seconds p. 32 - p. 35
Max voltage 10 VDC p. 32 - p. 35
Min voltage 2 VDC p. 32 - p. 35
Coil frost cutout temperature
30 °F p. 23
Condenser temperature control band:
Table 3. Factory presents (continued)
Adjustable Function Factory Preset Changed To Reference Page