Installation and Maintenance Manual

ECM Overview and Setup
44 UV-SVN02C-EN
The engine integrates a versatile configurable
auxiliary temperature sensor.
The engine incorporates various safety and lockout
features, suc
h as maintaining proper fan speeds, if
electric heat is called for.
Standard Adapter Board
The adapter allows direct customer interfacing
through the use of terminal strips. Standard
interfacing includes:
Fan Speeds (H, M, L) (for w
all mounted fan speed
switches)
Variable speed (0–10V) inputs
The standard adapter board elim
inates many separate
wiring harnesses in the panel and allows simple,
mistake-proofed single-plug interfacing of:
The ECM engine controller
Transformers
–Motors
Valves
–Dampers
Electric heat control
Fan speed switches
Main Power (except electric heat).
Electric heat lockout circuits an
d fan proving circuits
for electric heat are standard, and are pre-configured at
the factory.
CSTI Adapter Board
Performs all the functions of the standard adapter
module, but in addition, provides convenient field
connections to factory mounted end devices,
including:
Valves
–D
ampers
Electric Heat
Performs courtesy
inversion” of thermostatic inputs
to match selected valves:
Standard thermostats put out only “on” signals,
however customer may select a normally open
valve. A selectable switch allows the customer to
invert the thermostat outputs for correct operation.
These switches are set at the factory, but can be
adjusted in the field.
Sophisticated changeover function when used with
a thermistor, that replaces traditional bi-metallic
disc temperature switches:
Board will automatically honor only the
appropriate customer request (Heat/Cool)
depending on sensed water temperature.
Feature can be enabled or disabled with a
selector switch—however, it is set correctly at
the factory, based on customer choice of coil.
The bi-metallic disc temperature switch
emulation is programmable, and dead-band
range can be adjusted.
Electric heat lockout circuits and fan proving
circuits for electric heat are standard, and are
pre-configured at the factory.
Figure 41. Adapter board
Note: Customer Low-
Voltage
Interface for
Fan Speeds,
Variable Fan
Speed, and
24 Vac Supply
Figure 42. CSTI adapter board
1. Customer Low-Voltage Interface for Valves, Electric Heat, Dampers, Fan
Speeds, Variable Fan Speed, and 24 Vac Supply
2. Valve(s), Electric Heat, and Changeover Configuration Switches (Factory-
Set)
1
2