Installation and Maintenance Manual

Installation—Sensors
UV-SVN02C-EN 31
a. Hook the cover over the top of the back plate. Apply
light pressure to the bottom of the cover until it
snaps in place.
b. Install the security screw into the bottom of the
cover (if desired).
If installing a Tracer ZN520 zone sensor, see “Control
Options,” p. 28 for more information.
Wireless Sensors
Notes:
Receivers ship installed on the unit. To remove the
receiver, press in the retention tabs on the underside of
the receiver enclosure (see Figure 35) and push
upward.
For more detailed information for wireless sensors,
please refer to BAS-SVX04E-EN (Installation,
Operation, and Maintenance: Wireless Sensors,
Models WTS, WZS, and WDS), or the most recent
revision
Address Setting
The process of establishing communication between a
receiver and sensor is referred to as association. The
following limitations apply:
Each associated receiver/sensor set that
communicates within the reception range of the
wireless system must have a unique address.
It is not possible to associate more than one sensor to a
receiver, nor is it possible to associate more than one
receiver to a sensor.
To associate a receiver and sensor, the two devices must
have their rotary address switches set to the same
address.
Important: Set the addresses before applying power to
the receiver and before removing the
insulation strip (Figure 36) from the sensor.
To set the receiver and sensor addresses:
1. Using a small screwdriver, set the three rotary address
switches (locations S1, S2, S3) on the receiver to an
address between 001 and 999 (see Figure 36). You do
not have to remove the covers to access the rotary
address switches.
Figure 33.
Figure 34.
Security
screw
Figure 35. Retention tabs on underside of receiver
enclosure