Catalogue

64 UV-PRC004-EN
Mechanical Specifications
service tool connection. Wireless temperature sensors, which provide easy and flexible
installation, are a cost-effective alternative to wired sensors.
Some additional options available with the sensors include:
Easy-to-use display interface for clear and simple monitoring and control.
Temperature setpoint control to allow
the tenant to choose a temperature setpoint that satisfies
their personal preference.
Fan speed switch to allow the tenant to locally control the
fan speed to better satisfy their
preference.
Occupancy override to allow the tenant to request tem
porary timed override system operation
that keeps the building conditions in occupied comfort conditions.
COMM module that is compatible with all Trane
®
wired temperature sensors. This accessory
provides a local RJ22 connection to Trane
®
service tools for easy, low-cost maintenance.
Factory Mounted Piping (option)
Factory mounted piping is available when selecting Trane
®
controls or Customer Supplied
Terminal Interface (CSTI). Packages are available in 2-way or 3-way configurations with a 3-point
floating valve piped to the return side of the coil. Packages are leak tested to 90 psig to ensure joint
integrity.
Filter
Units equipped with a standard throwaway filter have an average resistance of 76 percent and dust
holding capacity of 26 grams per square foot.
Units equipped with 1-in. MERV 8 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with
ASHRAE Standard 52.1 atmospheric dust spot method.
Units equipped with 1-in. MERV 13 filters have a rating based on ASHRAE Standard 52.2. The
average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and
greater than 90 percent efficiency on 3–10 micron particles when tested in accordance with
ASHRAE Test Standard 52.2.
UV-PRC004-EN.book Page 64 Monday, February 4, 2013 11:01 AM