Catalogue
UV-PRC004-EN 33
Performance Data
Table 21. Steam coil capacity
Unit Size Coil Type EAT
TMBH
5 PSIG 10 PSIG 15 PSIG
075 K1 -20 85.89 89.98 93.48
0 78.94 83.04 86.54
20 72.00 76.10 79.59
40 65.06 69.16 72.65
60 58.12 62.21 65.71
70 54.65 58.74 62.24
K2 -20 101.18 106.01 110.12
0 93.00 97.83 101.94
20 84.82 89.65 93.77
40 76.64 81.47 85.59
60 68.46 73.29 77.41
70 64.38 69.20 73.32
100 K1 -20 112.93 118.31 122.91
0 103.80 109.19 113.78
20 94.67 100.06 104.65
40 85.54 90.93 95.52
60 76.41 81.80 86.40
70 71.85 77.24 81.83
K2 -20 158.08 165.61 172.05
0 145.30 152.84 159.27
20 132.52 140.06 146.49
40 119.74 127.28 133.71
60 106.96 114.50 120.93
70 100.57 108.11 114.55
125 K1 -20 139.94 146.61 152.31
0 128.63 135.30 140.99
20 117.31 123.99 129.68
40 106.00 112.68 118.37
60 94.69 101.36 107.06
70 89.03 95.71 101.40
K2 -20 164.93 172.79 179.50
0 151.60 159.46 166.17
20 138.26 146.13 152.84
40 131.78 132.80 139.51
60 111.60 119.47 126.18
70 104.93 112.80 119.51
150 K1 -20 166.93 174.89 181.68
0 153.44 161.40 168.19
20 139.94 147.90 154.70
40 126.45 134.41 141.20
60 112.96 120.92 127.71
70 106.21 114.17 120.96
K2 -20 243.70 256.14 263.74
0 224.72 236.38 246.33
20 204.96 216.62 226.57
40 185.20 196.86 206.80
60 165.43 177.09 187.04
70 155.55 167.21 177.16
200 K2 -20 286.51 306.05 317.93
0 266.20 282.43 294.32
20 244.09 258.82 270.71
40 221.28 235.21 274.09
60 197.66 211.59 223.48
70 185.86 199.79 211.67
Notes:
1. Condensate trap for the steam coil option is field installed.
2. Static pressure for the K1, K2 options should be modeled after the H1 coil option.
3. Steam coils that function at 5 psig or less should not utilize valve control. Valve control may starve the coil, causing
stratification.
K1-, K2-Steam Coils
UV-PRC004-EN.book Page 33 Monday, February 4, 2013 11:01 AM