Catalogue
UV-PRC004-EN 31
Performance Data
Table 19. R-410A cooling only
(a)
HUV
Unit Size Condensing Unit EWB (°F) T-Btu/hr
(b)
S-Btu/hr
EDB 72°F EDB 76°F EDB 80°F
075 4TTB3018 63 18865 12052 15467 18574
67 19919 7972 11532 15060
71 21029 3638 7170 10878
4TTB3024 63 23108 13307 16931 20805
67 24057 9023 12633 16291
71 25428 4477 7832 11784
100 4TTB3024 63 24820 15965 20784 24543
67 26117 10448 15251 19950
71 27544 4735 9536 14353
4TTB3030 63 28395 17201 21904 26087
67 29886 11643 16360 21069
71 31529 5709 10447 15301
125 4TTB3030 63 30441 19769 25504 30266
67 31903 12951 18875 24723
71 33583 5690 11569 17730
4TTB3036 63 35117 21393 27320 32571
67 36701 14277 20254 26132
71 38881 6927 13004 19506
150 4TTB3036 63 36851 23892 31008 36531
67 38641 15616 22735 29964
71 40353 6867 14159 21323
4TTB3042 63 41204 25231 32327 39155
67 42745 16873 23916 30966
71 44884 7964 15092 22325
200 4TTB3042 63 43734 30169 38934 43734
67 45733 19218 28689 38535
71 47505 7509 17362 26976
4TTB3048 63 47482 30769 39826 47125
67 49200 20140 29313 38635
71 51420 8828 17852 27549
(a) R-410A DX coils are rated at 95°F dry bulb/80°F wet bulb ambient outside air temperature, 25 feet of suction and liquid line, 400 cfm per Ton nominal.
(b)Total Capacity calculated from outdoor 95°F dry bulb/80°F wet bulb and 80°F indoor DB standard air conditions.
DX-Coils
UV-PRC004-EN.book Page 31 Monday, February 4, 2013 11:01 AM