Catalogue
30 UV-PRC004-EN
Performance Data
AHRI Cooling performance is based on 80/67 °F entering air temperature, 45°F entering chilled
water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temp, 180°F
entering water temperature with a 40°F ΔT. All performance measured on high speed tap, 115 V.
Free discharge units: 0.0 ESP, with throwaway filter. High static units: 0.20 ESP, without filter.
Table 17. R1-, R2-, GA-coils, 4-pipe with free discharge EC motor, heating data
Unit Size Coil Type
Heating
Total
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
075
R1 30.38 1.52 1.66
R2 36.27 1.81 2.29
GA 53.61 2.68 0.59
100
R1 38.03 1.90 0.54
R2 45.30 2.27 0.74
GA 72.06 3.60 1.14
125
R1 48.31 2.42 0.94
R2 57.62 2.88 1.30
GA 90.57 4.53 1.91
150
R1 68.42 3.42 1.36
R2 81.16 4.06 1.85
GA 102.98 5.15 2.63
200
R1 81.33 4.07 1.86
R2 96.80 4.84 2.56
GA 136.30 6.81 4.45
Table 18. R1-, R2-, DK-coils, 4-pipe with free discharge EC motor, cooling data
Unit Size Coil Type
Cooling
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
075
R1 26.73 18.60 5.33 3.85
R2 26.81 18.21 5.34 3.87
DK 17.47 13.97 3.48 1.27
100
R1 32.41 21.82 6.46 6.49
R2 34.38 22.76 6.85 7.21
DK 23.03 16.94 4.59 2.47
125
R1 41.81 29.35 8.33 4.46
R2 46.51 31.39 9.27 5.40
DK 33.47 24.34 6.67 5.55
150
R1 50.24 34.23 10.01 6.96
R2 54.23 35.59 10.81 7.98
DK 40.17 28.34 8.01 8.71
200
R1 62.56 43.67 12.47 10.31
R2 67.07 44.90 13.35 11.67
DK 48.70 35.47 9.71 12.26
GA-, DK-, R1-, R2-Coils