Performance Data
AHRI Cooling performance is based on 80/67° F entering air temperature, 45°F entering chilled
water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temp, 180°F
entering water temperature with a 40°F ΔT. All performance measured on high speed tap, 115 V.
Free discharge units: 0.0 ESP, with throwaway filter. High static units: 0.20 ESP, without filter.
Table 15. 2-Pipe coil, HW data
HUV Size Coil Type
Heating
Total
Capacity Flow Rate WPD
(MBh) (gpm) (ft H
2
0)
075
H1 41.18 2.06 2.85
H2 45.12 2.26 3.36
H3 48.74 2.44 3.86
H4 53.49 2.67 0.70
H5 57.95 2.90 0.81
H6 61.84 3.09 0.91
100
H1 52.90 2.65 0.97
H2 57.98 2.90 1.15
H3 62.65 3.13 1.33
H4 71.90 3.59 1.41
H5 77.92 3.90 1.63
H6 83.19 4.16 1.84
125
H1 66.45 3.32 1.67
H2 72.85 3.64 1.98
H3 78.73 3.94 2.28
H4 90.36 4.52 2.45
H5 97.97 4.90 2.83
H6 104.61 5.23 3.19
150
H1 99.89 4.99 2.70
H2 124.35 6.22 4.03
H3 131.66 6.58 4.48
H4 108.87 5.44 3.88
H5 118.05 5.90 4.49
H6 126.08 6.30 5.05
200
H1 120.35 6.02 3.80
H2 152.05 7.60 5.84
H3 161.68 8.08 6.54
H4 132.52 6.63 5.52
H5 144.37 7.22 6.44
H6 154.87 7.74 7.32
Table 16. X-coils, 2-pipe with free discharge EC motor
Size Coil Type
Cooling
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
075
X3 26.73 18.60 5.33 3.85
X4 26.73 18.60 5.33 3.85
X6 26.73 18.60 5.33 3.85
100
X3 32.41 21.82 6.46 6.49
X4 32.41 21.82 6.46 6.49
X6 32.41 21.82 6.46 6.49
125
X3 39.67 27.73 7.91 7.51
X4 39.67 27.73 7.91 7.51
X6 39.67 27.73 7.91 7.51
150
X3 50.24 34.23 10.01 6.96
X4 50.24 34.23 10.01 6.96
X6 50.24 34.23 10.01 6.96
200
X3 72.21 48.78 14.39 13.34
X4 72.21 48.78 14.39 13.34
X6 72.21 48.78 14.39 13.34
H-, X-Coils