Catalogue
UV-PRC004-EN 27
Performance Data
A-Coils
AHRI Cooling performance is based on 80/67°F entering air temperature, 45°F entering chilled
water temperature with a 10°F ΔT. Heating performance is based on 70°F entering air temp, 180°F
entering water temperature with a 40°F ΔT. All performance measured on high speed tap, 115 V.
Free discharge units: 0.0 ESP, with throwaway filter. High static units: 0.20 ESP, without filter.
Table 11. A-Coils, 2-pipe coil with free discharge EC motor
Size Coil Type
Airflow
(cfm)
Cooling Heating
Motor
Power
(W)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
Total
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
075
AA 875 19.12 15.62 3.81 1.49 52.00 2.60 0.70 135
AB 825 21.80 16.49 4.34 1.88 57.80 2.89 0.80 135
AC 815 27.63 19.28 5.51 4.09 63.90 3.19 1.40 135
AD 780 21.13 16.70 4.21 0.67 67.20 3.36 0.40 135
AE 760 19.64 15.28 3.91 0.59 71.70 3.58 0.50 135
100
AA 1090 25.18 9.02 5.02 2.89 67.00 3.35 1.20 180
AB 1030 28.47 20.09 5.67 3.60 74.40 3.72 1.50 180
AC 1025 33.88 22.89 6.75 7.02 81.90 4.09 2.50 180
AD 975 30.23 21.17 6.02 1.49 96.60 4.33 0.70 180
AE 1015 32.03 21.56 6.38 1.65 97.30 4.87 0.90 180
125
AA 1240 33.47 25.57 6.67 5.55 79.00 3.95 1.90 191
AB 1300 40.07 28.39 7.99 7.64 94.40 4.75 2.70 191
AC 1290 42.72 30.03 8.51 4.45 101.20 5.06 1.60 191
AD 1240 46.56 31.33 9.28 3.66 110.70 5.54 1.30 191
AE 1265 48.38 31.40 9.64 3.93 122.30 6.11 1.60 191
150
AA 1600 42.25 31.85 8.42 9.53 100.30 5.01 3.30 221
AB 1525 46.68 32.38 9.30 11.38 112.10 5.60 4.10 221
AC 1510 50.09 34.12 9.98 6.66 119.90 5.99 2.40 221
AD 1600 56.11 36.64 11.18 5.70 141.80 7.09 2.30 221
AE 1485 56.68 35.73 11.30 5.81 144.80 7.24 2.30 221
200
AA 2085 51.50 40.18 10.26 13.55 120.00 6.00 4.60 311
AB 1985 58.90 42.59 11.74 17.21 135.40 6.77 5.70 311
AC 1970 64.10 44.91 12.78 10.34 146.40 7.32 3.40 311
AD 1885 71.18 47.35 14.19 8.78 161.70 8.08 2.90 311
AE 1785 70.97 45.41 14.14 8.73 169.30 8.47 3.10 311
Table 12. A-coil, 2-pipe coil with high static EC motor
Size Coil Type
Airflow
(cfm)
Cooling Heating
Motor
Power
(W)
Total
Capacity
(MBh)
Sensible
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
Total
Capacity
(MBh)
Flow Rate
(gpm)
WPD
(ft H
2
0)
075
AA 780 17.24 14.07 3.44 1.24 48.00 2.40 0.60 198
AB 760 20.09 15.16 4.00 1.62 54.40 2.72 0.70 198
AC 755 25.81 17.92 5.14 3.62 60.20 3.01 1.20 198
AD 740 18.96 15.35 3.78 0.55 64.20 3.21 0.40 198
AE 795 22.56 16.92 4.50 0.76 74.50 3.73 0.50 198
100
AA 1115 28.38 21.70 5.66 3.57 68.00 3.40 1.30 287
AB 1090 32.67 23.42 6.51 4.59 77.50 3.88 1.60 287
AC 1085 38.77 26.52 7.73 8.91 85.50 4.28 2.70 287
AD 1055 37.26 25.97 7.43 2.17 92.40 4.62 0.80 287
AE 1005 36.82 24.68 7.34 2.13 96.40 4.82 0.90 287
125
AA 1255 34.55 26.50 6.88 5.87 79.60 3.98 2.00 305
AB 1225 39.67 28.07 7.91 7.51 90.40 4.52 2.50 305
AC 1220 42.27 29.69 8.42 4.37 96.90 4.85 1.40 305
AD 1350 51.35 34.70 10.23 4.38 118.70 5.93 1.50 305
AE 1295 51.45 33.47 10.25 4.39 124.80 6.24 1.60 305
150
AA 1490 37.40 27.72 7.45 7.68 95.40 4.77 3.10 357
AB 1450 42.55 29.09 8.48 9.65 108.00 5.40 3.80 357
AC 1445 45.63 30.84 9.09 5.65 115.80 5.79 2.20 357
AD 1715 55.74 36.38 11.11 5.63 150.00 7.50 2.50 357
AE 1635 55.39 34.88 11.04 5.57 157.20 7.86 2.70 357
200
AA 2095 50.67 39.43 10.10 13.16 120.40 6.02 4.60 770
AB 2005 57.94 41.78 11.55 16.71 136.40 6.82 5.80 770
AC 1990 62.87 43.94 12.53 9.99 147.40 7.37 3.40 770
AD 1895 69.14 45.88 13.78 8.32 162.40 8.12 2.90 770
AE 1770 68.74 43.88 13.70 8.24 168.10 8.40 3.10 770
UV-PRC004-EN.book Page 27 Monday, February 4, 2013 11:01 AM