Split System Heat Pump Product Data XB14 4TWB4 1 1/2 - 5 Tons PUB. NO.
Features and Benefits • CLIMATUFF® compressor • Efficiency up to 16.0 SEER and 8.
Contents Features and Benefits 2 General Data 4 Product Specifications A-weighted Sound Power Level [dB(A)] Accessory Description and Usage AHRI Standard Capacity Rating Conditions Model Nomenclature Electrical Data Dimensions Mechanical Specification Options 22-1834-09 3 4 4 6 6 7 8 15 16
General Data Product Specifications Model No. 1 Electrical Data V/Ph/Hz 2 Min Cir Ampacity Max Fuse Size (Amps) Compressors RL AMPS - LR AMPS Outdoor Fan FL Amps Fan HP Fan Dia (inches) Coil Refrigerant R-410A Line Size - (in.) O.D. Gas 3 Line Size - (in.) O.D.
General Data Product Specifications Model No. 1 4TWB4042E1 Electrical Data V/Ph/Hz 2 208/230/1/60 Min Cir Ampacity 27 Max Fuse Size (Amps) 45 Compressors CLIMATUFF® - SCROLL RL AMPS - LR AMPS 19.9 - 109 Outdoor Fan FL Amps 0.93 Fan HP 1/5 Fan Dia (inches) 27.6 Coil Spine Fin™ Refrigerant R-410A 12/1-LB/OZ Line Size - (in.) O.D. Gas 3 3/4 Line Size - (in.) O.D. Liquid 3 3/8 Dimensions H x W x D (Crated) 46.4 x 35.1 x 38.
General Data Accessory Description and Usage AHRI Standard Capacity Rating Conditions Anti-Short Cycle Timer — Solid state timing device that prevents compressor recycling until 5 minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc. AHRI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil.
Model Nomenclature Outdoor Units Gas Furnaces 4 T W B 4 0 3 6 G 1 0 0 0 A A T U D 2 B 0 8 0 A C V 3 2 A A Refrigerant Type 2 = R-22 4 = R-410A TRANE Product Type W = Split Heat Pump T = Split Cooling Product Family Z = Leadership – Two Stage X = Leadership R = Replacement/Retail B = Basic A = Light Commercial Family SEER 0 = 10 3 = 13 1 = 11 4 = 14 2 = 12 5 = 15 6 = 16 8 = 18 9 = 19 Split System Connections 1-6 Tons 0 = Brazed Nominal Capacity in 000s of BTUs Major Design Modifications Power Supply 1
Electrical Data Schematic Diagrams 4TWB4018, 4TWB4024, 4TWB4036 Printed from D156770P01 Rev 00 8 22-1834-09
Electrical Data Schematic Diagrams 4TWB4030 Printed from D157099P01 22-1834-09 9
Electrical Data Schematic Diagrams 4TWB4042 TDR relay cycles sump heat off during compressor operation and delays energizing the sump heat for 30 mins after “Y” call is removed.
Electrical Data Schematic Diagrams 4TWB4048 TDR relay cycles sump heat off during compressor operation and delays energizing the sump heat for 30 mins after “Y” call is removed.
Electrical Data Schematic Diagrams (SEE LEGEND) 4TWB4049E TDR relay cycles sump heat off during compressor operation and delays energizing the sump heat for 30 mins after “Y” call is removed. PRINTED FROM D156976P01 REV.
Electrical Data Schematic Diagrams 4TWB4060 TDR relay cycles sump heat off during compressor operation and delays energizing the sump heat for 30 mins after “Y” call is removed.
Electrical Data Schematic Diagrams (SEE LEGEND) 4TWB4061E TDR relay cycles sump heat off during compressor operation and delays energizing the sump heat for 30 mins after “Y” call is removed. PRINTED FROM D154974P02 REV.
Dimensions 4TWB4 Outline Drawing Note: All dimensions are in MM (Inches).
Mechanical Specification Options General The 4TWB4 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer.