Product Data Split System Cooling 4TTR3018H1000N 4TTR3024H1000N 4TTR3030H1000N 4TTR3036H1000N 4TTR3042E1000N 4TTR3048E1000N 4TTR3060D1000N August 2016 22-1842-8D-EN
Product Specifications Model No. (a) 4TTR3018H1000N 4TTR3024H1000N 4TTR3030H1000N 4TTR3036H1000N 208/230/1/60 208/230/1/60 208/230/1/60 208/230/1/60 MIN. BRCH. CIR. AMPACITY 12 17 16 18 BR. CIR. PROT. RTG. — MAX. (AMPS) 20 25 25 30 CLIMATUFF®SCROLL CLIMATUFF®SCROLL CLIMATUFF®SCROLL CLIMATAUFF®SCROLL RL AMPS — LR AMPS 9 — 48 12.8 — 58.3 12.3 — 63 14.1— 75 Outdoor Fan FL AMPS 0.64 0.64 0.9 0.7 Fan HP 1/8 1/8 1/8 1/8 Fan Dia (inches) 23.0 23.0 18.9 23.
Pr o d u c t S p e c i fi c a ti o n s Model No. (a) POWER CONNS. — V/PH/HZ 4TTR3042E1000N 4TTR3048E1000N 4TTR3060D1000N 280/230/1/60 280/230/1/60 280/230/1/60 MIN. BRCH. CIR. AMPACITY 22 28 35 BR. CIR. PROT. RTG. — MAX. (AMPS) 35 45 60 CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL RL AMPS — LR AMPS 17.0 — 124 21.8 — 117 26.8 — 134 Outdoor Fan FL AMPS 0.7 0.93 0.93 Fan HP 1/8 1/5 1/5 Fan Dia (inches) 23 23 27.
Accessory Description and Usage A n t i - S h o rt C y c l e T i m e r — Solid state timing device that prevents compressor recycling until five (5) minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power delivery, commercial applications, long lineset, etc. E v a p o r a t i o n D e f r o s t C o n t r o l — SPST Temperature actuated switch that cycles the condenser off as indoor coil reaches freeze-up conditions. Used for low ambient cooling to 30°F with TXV.
Schematic Diagrams Figure 1. 1.5 — 4.
S ch e m a t i c D i a g r a m s Figure 2. 5.
Outline Drawing Model Base A B C D E F G H J K 4TTR3018H 2 730 (28–3/4) 724 (28–1/2) 651 (25–5/8) 3/4 3/8 127 (5) 57 (2–1/4) 194 (7–5/8) 38 (1–1/2) 457 (18) 4TTR3024H 2 730 (28–3/4) 724 (28–1/2) 651 (25–5/8) 3/4 3/8 137 (5–3/8) 65 (2–5/8) 210 (8–1/4) 57 (2–1/4) 457 (18) 4TTR3030H 2 730 (28–3/4) 724 (28–1/2) 651 (25–5/8) 3/4 3/8 137 (5–3/8) 65 (2–5/8) 210 (8–1/4) 57 (2–1/4) 457 (18) 4TTR3036H 3 730 (28–3/4) 829 (32–5/8) 756 (29–3/4) 3/4 3/8 137 (5–3/8)
Mechanical Specification Options General The Outdoor Units are fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.