Split System Heat Pump Product & Performance Data XB 13 2TWB3018-060 1½ – 5 Tons PUB. NO.
Features and Benefits • Climatuff® compressor • Demand Defrost Control • All aluminum Spine Fin™ coil • Easy top & fan removal • DuraTuff™ base, fast complete drain, weather proof • R-22 refrigerant (Not Factory Supplied) • Polyslate gray cabinet high gloss with fan motor cover • Low ambient cooling to 55°F as shipped • Quick-Sess™ cabinet, easy service access and refrigerant connections with full coil protection • Low ambient cooling to 40°F with EDC accessory AY28X084 • Corrosion resistant fini
Contents Features and Benefits 2 General Data 4 Product Specifications A-weighted Sound Power Level [dB(A)] Accessory Description and Usage AHRI Standard Capacity Rating Conditions Model Nomenclature 6 Electrical Data 7 Dimensions 9 Mechanical Specification Options 22-1771-04 4 4 5 5 3 10
General Data Product Specifications Model No. 1 2TWB3018A1 Electrical Data V/Ph/Hz 2 200/230/1/60 Min Cir Ampacity 8 Max Fuse Size (Amps) 15 Compressor CLIMATUFF ® RL Amps - LR Amps 5.9 - 38.6 Outdoor Fan FL Amps 0.6 Fan HP 1/15 Fan Dia (inches) 19.0 Coil Spine Fin™ Refrigerant R-22 (Not Factory Supplied) 5/10-LB/OZ 5/8 Line Size - (in.) O.D. Gas 3 1/4 Line Size - (in.) O.D. Liquid 3 Dimensions H x W x D (Crated) 37.2 x 26.
General Data Product Specifications Model No. 1 Electrical Data V/Ph/Hz 2 Min Cir Ampacity Max Fuse Size (Amps) Compressor RL Amps - LR Amps Outdoor Fan FL Amps Fan HP Fan Dia (inches) Coil Refrigerant R-22 (Not Factory Supplied) Line Size - (in.) O.D. Gas 3 Line Size - (in.) O.D.
Model Nomenclature Outdoor Units 2 T W B 3 0 3 6 A 1 0 0 0 A A High Efficiency Furnaces Furnace Configuration TU = Upflow / Horizontal TD = Downflow / Horizontal Type D = 80% Premium X = 90% Premium Refrigerant Type 2 = R-22 4 = R-410A TRANE Product Type W = Split Heat Pump T = Split Cooling Number of Heating Stages 1 = Single Stage 2 = Two Stage 3 = Three Stage Cabinet Width A = 14.5" Cabinet Width B = 17.5" Cabinet Width C = 21.0" Cabinet Width D = 24.
Electrical Data Schematic Diagrams (SEE LEGEND) 2TWB3018,024,030,036,042A 2TWB3048A Printed from D155596P01 Printed from D155595P01 22-1771-04 7
Electrical Data Schematic Diagrams 2TWB3060A LEGEND SYMBOLS 8 22-1771-04
Dimensions 2TWB3 Outline Drawing MODELS BASE FIG.
Mechanical Specification Options General The 2TWB3 is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Casing Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder paint on all louvers, panels, prepaint on all other panels.