Installation Guide
Table Of Contents
9 
exceed 75% relative humidity. (ASTM F2170 - Standard Test Method for Determining 
Relative Humidity in Concrete Floor Slabs Using In Situ Probes). 
9.5 Testing for Alkalinity - Testing the pH at the surface of a concrete slab must be 
conducted in accordance with ASTM F 710-05 “, not to exceed 9 pH . (ASTM F710-05 - 
Standard Practice for Preparing Concrete Floors to Receive Resilient Flooring). 
Note: Preparing the surface of a concrete slab for pH testing can be 
problematical. Make sure the concrete surface is adequately cleaned of 
adhesives, curing compounds etc. When pH readings are less than 8.5, it may 
be an indication of a residue remaining on the concrete surface. Also use care 
not to over clean the surface of the concrete, consequently removing the 
(usually) thin layer of carbonation. This can result in pH readings >12. 
Caution: The results obtained from testing reflect only the condition of the 
concrete floor at the time of testing. Further, it is highly recommended that 
the test site or building be at the same temperature and humidity expected 
during normal use. These conditions are required to be maintained 48 hrs 
prior to, and during testing. The installation of a permanent, effective 
moisture vapor retarder with a minimum thickness of 0.010 inch and a 
permanency of 0.1 perms, as described in ASTM Specification E 1745, is 
required under all on-grade or below-grade concrete floors. 
10.  Relaxing/Conditioning Carpet – To minimize wrinkling and buckling and to 
facilitate installation, it is highly recommended that carpet be unrolled and allowed to 
relax in the installation area for a time period that conforms to the requirements of 
the manufacturer of the product being installed. (See Section 7.2 Ambient 
Conditions) This time period will vary up to 72 hours, but should not be less that 24 
hours at a temperature between 65-95ºF (18 -35ºC). Protect carpet adequately from 
soil, dust, moisture and other contaminants.  Sundry items, such as adhesives, should be 
conditioned as well. 
If these conditions are not attainable, contact flooring manufacturer 
for applications to warranty. 
Note: The allocation of time for the relaxation period should be included in the planning of the 
job by all interested parties. 
11.  Ventilation - During installation, maintain air circulation by operating the HVAC 
system at full capacity.  
  Note: For acceptable indoor air quality, fresh air ventilation in commercial spaces is 
recommended to conform to current guidelines specified in ASHRAE Standard 62 published by 
the American Society of Heating, Refrigerating and Air Conditioning Engineers 
(www.ashrae.org
). Failure to comply could cause negative ramifications to the installation and 
the indoor air quality. 
12.  Carpet Seam Edge Preparation 










