TSP–BCM24 Battery Controller Module
This module provides a professional battery management system to charge and
monitor an external lead-acid battery. Together with a power supply of the TSP
series a perfect DC-UPS system can be configured. The connected battery will be
charged and held in charged mode by the power supply. In case of a mains power
failure the battery will supply the output power until the battery is discharged. As a
consequence, the output voltage of the system is equivalent to the battery voltage.
To avoid overcharging the battery, an external temperature sensor adjusts the bat-
tery voltage automatically to the required end of charge voltage. By this, the battery
life time can be extended.
The battery is protected against deep discharge. Mains power and the battery
status are checked and monitored continuously and failures are indicated by corre-
sponding LED’s and alarm outputs. The module provides also an external On/Off
input to switch-off both, power supply and battery.
Order code
(includes terminal plugs)
Inputs Input Power
max
Output Voltage
nom.
*Output Power
max.
TSP-BCM24
24 VDC Power Supply
and 24 VDC Battery
360 W
24 VDC 360 W
Models
*reduce max. output current by battery charging current
Function Diagram Connector Positions
Battery Controller
TSP
Temp.
Sensor (TS)
Volt adjust
Output
Load
DC-OK
in
p
ut
+
_
J1.2
J1.1
J3.1
J3.2
J5.1 J5.2
J2.2
J2.1
J2.4
J2.3
+
_
DC IN
Remote
Link
24V Battery
+
_
BAT.-OK
J5.3 J5.4
DC-OK
out
p
ut
J5.5 J5.6
Remote
On/Off
J5.7 J5.8
T
Fuse
J5.9 J5.10
J1.4
J1.3
Power
Supply
Front view Bottom view Top view
AC OK
Bat. OK
DC OK
Temp. Sensor
(TS)
DC IN Battery
-
+
-
+
Output
- -
+ +
Remote Link
Remote On/Off
Specifications
Operating temperature – 25°C...+70°C max. (13°F...+158°F)
derating above 40°C (104°F): 1.5%/K
Electromagnetic compatibility in correspondence to connected units (no internal
switching device)
Battery protection over voltage, deep discharge, overcharge, short circuit-
and revers connection (built-in fuse)
Status signals DC-OK input, DC-OK output, BAT OK
all relay contact closed at status OK
Rating per relay contact 30 VDC / 1.0 A max.
Dimensions same as model TSP 090 (see page 10)
Remote link cable (0.5m) 1 cable included with TSP-BCM24 module
Remote On/Off by ext. contact: contact open = On, contact closed = Off