Datasheet

http://www.tracopower.com Page 4 of 13
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TSP Series 90600 Watt
General Specifications
Operating temperature range – 25°C...+70°C max. (13°F...+158°F)
(for derating see graph A on page 5)
Cooling convection cooling, no internal fan
Storage temperature 25 °C…+85 °C (– 13°F...+185°F)
Humidity (non condensing) 95 % rel. H max.
Pollution degree 2
Temperature coefficient 0.02 %/K
Reliability, calculated MTBF @ 25°C acc. to IEC 61709
– TSP 070/090 >1.8 Mio h
– TSP 140 >1.2 Mio h
– TSP 180/360/600 >0.9 Mio h
Remote On/Off by ext. contact.
DC on: -S contact open
DC off: -S connectetd via 1Kohm to -Vout
Isolation according to IEC/EN 60950-1, UL 60950-1, UL 508
Safety standards
– Information technology equipment
IEC/EN 60950-1, UL 60950-1, CSA-C22.2 No. 60950-1-03
– Industrial control equipment UL 508,
CSA-C22.2 No. 107
– Electrical equipment of machines EN 60204
– Electronic equipment for power installation EN 50178
– Safety transformers for SMPS EN 61558-2-4
– Limited power source (model TSP 090-124N) EN 60950 sect. 2.5 and NEC Class 2
– Control equipment for hazardous location UL 60079-15
(Class I, Division 2, Groups A,B,C,D AEx n C II C T4 U)
IEC/EN 60079-15 (Class I, Zone 2, EEx nC II C T4 U),
(
II3G EEX nAC IIC (T4)
Safety approvals and – CB report for IEC 60950-1
certifications
www.tracopower.com/products/tsp-cb.pdf
– UL approvals UL 60950-1 rec. File: E181381, UL 508C listed File: E210002
www.ul.com -> certifications
– CSA certification (file no. 219759) for UL 60950-1, UL 508, UL 60079-15-02,
ANSI/ISA 12.12.01, CSA-22.2 No. 60950-1-03,
CSA C22.2 No. 107, CSA 60079-15-02
www.tracopower.com/products/tsp-csa.pdf
II3G ATEX 94/9/EC certificate no. SEV 05 ATEX 0146 U (option -EX only)
www.tracopower.com/products/tsp-atex.pdf
– GS certification for EN 60950-1, EN 60204, EN 61558-2-4
www.tracopower.com/products/tsp-gs.pdf
Class of protection safety class I (IEC 536)
Degree of protection IP 20
(IEC/EN 60529)
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Electrostatic discharge (ESD) IEC / EN 61000-4-2 4 kV / 8 kV criteria B
– Radiated RF field immunity IEC / EN 61000-4-3 10 V / m criteria B
– Electrical fast transient / burst immunity IEC / EN 61000-4-4 2 kV criteria B
– Surge immunity IEC / EN 61000-4-5 1 kV / 2 kV criteria B
– Immunity to conducted RF disturbances IEC / EN 61000-4-6 10 V criteria B
– Power frequency field immunity IEC / EN 61000-4-8 30 A / m criteria B
– Mains voltage dips and interruptions IEC / EN 61000-4-11 criteria B/C
– Voltage sag immunity SEMI F47
www.tracopower.com/products/TSP_SemiF47.pdf