Datasheet
http://w ww.tracopower.com Page 3 of 4
General Specifications
Safety standards IEC 60950-1, EN 60950-1 (output SELV),
UL 60950-1, UL 508, EN 50178,
EN 60204, EN 61558-2-8.
Safety approvals – CB scheme (IEC 60950-1) www.tracopower.com/products/tpc-cb.pdf
– UL listing UL 508C listed, CSA C22.2 No. 14
File e210002
www.ul.com -> certifications
– UL recognition (entry pending) UL 60950, File e181381
www.ul.com -> certifications
– CSA certification UL 60950-1, CSA 60950-1-03
www.tracopower.com/products/tpc-csa.pdf
– BG certificate (by SIQ) (IEC/EN 60950-1) www.tracopower.com/products/tpc-bg.pdf
Environmental compliance – Reach www.tracopower.com/products/tpc-reach.pdf
– RoHS RoHS directive 2011/65/EU
Electromagnetic compatibility (EMC), emissions EN 61000-6-3 (residential environment)
Electromagnetic compatibility (EMC), immunity EN 61000-6-2 (industrial environment)
Class of protection class I (earth connection needed)
Case protection IP 20 (IEC 60529)
Enclosure material Makrolon 2405 (UL 94V-0 rated)
Mounting DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
wall mounting bracket optional
Installation instructions www.tracopower.com/products/tpc-inst.pdf
Industrial Power Supplies
TPC Series 30 to 120 Watt
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
TPC–REM240-24 Redundancy Module
These modules are external units for operation with two TPC power supplies with
output voltage of 24 VDC or 48 VDCand of same type and power. The modules
allow to connect two outputs of TPC power supplies together in order to achieve a
reliable DC supply. In normal operation the module achieves equal current share
for both power supplies connected. During the redundancy operation, if one of
the power supplies fails, the output power will be provided in full by the remain-
ing operating power supply. The redundancy of the DC system is monitored by a
DC-OK signal.
Order Code Nominal Input
Voltage
Max Power
per Input
Output Voltage
adjustable
Output Current
max.
TPC–REM240–24
24 VDC
120 W
24 – 27 VDC
10 A
TPC–REM240–48
48 VDC 48 – 55 VDC
5 A
Specifications
Operating temperature –25°C to +50°C max.
Electromagnetic compatibility in correspondence to connected units
(no internal switching device)
Dimensions same as model TPC 055 (see page 4)
Connection screw terminal block
Installation instructions www.tracopower.com/products/tpc-rem-inst.pdf
pending
pending