Datasheet

Safety Standards
- IT / Multimedia Equipment
EN 60950-1
EN 62368-1
IEC 60950-1
IEC 62368-1
UL 60950-1
UL 62368-1
- Industrial Control Equipment
UL 508
- Medical Equipment
EN 60601-1
IEC 60601-1
ANSI/AAMI ES 60601-1
CSA-C22.2, No 60601-1
2 x MOPP (Means Of Patient Protection)
- Certification Documents
www.tracopower.com/overview/tmm60c
Protection Class
Class I & II (Prepared): Reinforced Insulation
Pollution Degree
PD 2
Over Voltage Category
OVC II
Safety Specifications
EMI Emissions
EN 61000-6-3 (Generic Residential)
EN 61000-6-4 (Generic Industrial)
- Conducted Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 15 class B (internal filter)
- Radiated Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 15 class B (internal filter)
EMS Immunity
EN 55024 (IT Equipment)
EN 55035 (Multimedia)
EN 61000-6-1 (Generic Residential)
EN 61000-6-2 (Generic Industrial)
EN 60601-1-2 edition 4 (Medical Devices)
- Electrostatic Discharge
Air:
EN 61000-4-2, ±15 kV, perf. criteria A
Contact:
EN 61000-4-2, ±8 kV, perf. criteria A
- RF Electromagnetic Field
EN 61000-4-3, 10 V/m, perf. criteria A
- EFT (Burst) / Surge
EN 61000-4-4, ±2 kV, perf. criteria A
L to L:
EN 61000-4-5, ±1 kV, perf. criteria A
- Conducted RF Disturbances
EN 61000-4-6, 10 Vrms, perf. criteria A
- PF Magnetic Field
Continuous:
EN 61000-4-8, 30 A/m, perf. criteria A
- Voltage Dips & Interruptions
230 VAC / 50 Hz:
30%, 25 periods, perf. criteria A
>95%, 0.5 periods, perf. criteria A
>95%, 1 period, perf. criteria A
>95%, 250 periods, perf. criteria B
EMC Specifications
Relative Humidity
95% max. (non condensing)
Temperature Ranges
- Operating Temperature
–40°C to +80°C
- Storage Temperature
–40°C to +95°C
Power Derating
- High Temperature
4.5 %/K above 60°C (5 Vin model)
3.8 %/K above 60°C (other models)
See application note:
www.tracopower.com/overview/tmm60c
Cooling System
Natural convection (20 LFM)
Altitude During Operation
5'000 m max.
Switching Frequency
100 kHz typ. (PWM)
Insulation System
Reinforced Insulation
Working Voltage (rated)
240 VAC
Isolation Test Voltage
- Input to Output, 60 s
4'000 VAC
General Specifications
TMM 60C Series, 60 Watt
All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated.
www.tracopower.com September 20, 2023
Page 3 / 4