Datasheet
Hold-up Time
- At 230 VAC
50 ms min.
- At 115 VAC
10 ms min.
Start-up Overshoot Voltage
5% max.
Short Circuit Protection
Continuous, Automatic recovery
Output Current Limitation
105% min. of Iout max.
Overvoltage Protection
120% typ. of Vout nom.
(By Zener diode)
Safety Standards
- IT / Multimedia Equipment
EN 60950-1
EN 62368-1
IEC 60950-1
IEC 62368-1
UL 60950-1
UL 62368-1
- Industrial Control Equipment
UL 508
- Medical Equipment
EN 60601-1
IEC 60601-1
ANSI/AAMI ES 60601-1
CSA-C22.2, No 60601-1
2 x MOPP (Means Of Patient Protection)
- Certification Documents
www.tracopower.com/overview/tmm40c
Protection Class
Class I & II (Prepared): Reinforced Insulation
Pollution Degree
PD 2
Over Voltage Category
OVC II
Safety Specifications
EMI Emissions
EN 61000-6-3 (Generic Residential)
EN 61000-6-4 (Generic Industrial)
- Conducted Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 15 class B (internal filter)
- Radiated Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 15 class B (internal filter)
EMS Immunity
EN 55024 (IT Equipment)
EN 55035 (Multimedia)
EN 61000-6-1 (Generic Residential)
EN 61000-6-2 (Generic Industrial)
EN 60601-1-2 edition 4 (Medical Devices)
- Electrostatic Discharge
Air:
EN 61000-4-2, ±15 kV, perf. criteria A
Contact:
EN 61000-4-2, ±8 kV, perf. criteria A
- RF Electromagnetic Field
EN 61000-4-3, 10 V/m, perf. criteria A
- EFT (Burst) / Surge
EN 61000-4-4, ±2 kV, perf. criteria A
L to L:
EN 61000-4-5, ±1 kV, perf. criteria A
- Conducted RF Disturbances
EN 61000-4-6, 10 Vrms, perf. criteria A
- PF Magnetic Field
Continuous:
EN 61000-4-8, 30 A/m, perf. criteria A
- Voltage Dips & Interruptions
230 VAC / 50 Hz:
30%, 25 periods, perf. criteria A
>95%, 0.5 periods, perf. criteria A
>95%, 1 period, perf. criteria A
>95%, 250 periods, perf. criteria B
EMC Specifications
Relative Humidity
95% max. (non condensing)
Temperature Ranges
- Operating Temperature
–40°C to +80°C
- Storage Temperature
–40°C to +95°C
General Specifications
TMM 40C Series, 40 Watt
All specifications valid at nominal voltage, resistive full load and +25°C after warm-up time, unless otherwise stated.
www.tracopower.com September 20, 2023
Page 3 / 5