www.tracopower.com Page 3 of 6
TIB 080EX Series, 80 Watt
General Specifications
Operating temperature range –40°C to +70°C max.
Derating 2 %/K above +60°C
Cooling convection cooling, no internal fan
Overtemperature protection switch off at overtemperature
Humidity (non condensing) 5–95 % rel. H max.
Altitude during operation 2000 m max.
Isolation Voltage – Input/Ouput 4250 VDC
– Input/Chassis 1500 VDC
– Ouput/Chassis 750 VDC
Creepage Clearance – Input/Ouput 8 mm
– Input/Chassis 4 mm
– Output/Chassis 1.5 mm
MTBF (acc. to IEC 61709 at 25°C) > 1‘950‘000 h
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1
CSA 22.2 No 60950-1-03
– Safety low voltage switchgear and controlgear UL 508
– ATEX for hazardous location EN 60079-15, EN 60079-15, EN 60079-15
(EX II3G Ex ec nC IIC GC)
– UL HazLoc Class I, Division 2
– Certification documents www.tracopower.com/overview/tib
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted emission input EN 55032, EN 55011 class B
– Radiated RI emission EN 55032, EN 55011 class B
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Railway applications signalling apparatus EN 50121- 4
– Railway applications rolling stock apparatus EN 50121-3-2
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 4 kV/8 kV criteria A
– Radiated RF field immunity IEC/EN 61000-4-3 10 V/m criteria A
– Electrical fast transient / burst immunity IEC/EN 61000-4-4 2 kV criteria B
– Surge immunity IEC/EN 61000-4-5 1 kV/2 kV criteria B
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria A
– Power frequency field immunity IEC/EN 61000-4-8 30 A/m criteria A
– Mains voltage dips and interruptions IEC/EN 61000-4-11 criteria B/C
– Voltage sag immunity SEMI F47 (230 VAC) criteria A
Environment – Railway applications shock and vibration according EN 61373
– Vibration acc. IEC 60068-2-6-3 3 axis, 2 g sine sweep, 10–55 Hz, 11 okt/min
– Shock acc. IEC 60068-2-27 3 axis, 25 g half sine, 11 ms
Enclosure material – Chassis aluminium
– Cover stainless steel
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-3515/7.5
Environmental compliance – Reach www.tracopower.com/products/reach-declaration.pdf
– RoHS RoHS directive 2011/65/EU
Connection screw terminals
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.