Datasheet
http://www.tracopower.com Page 3 of 5
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
General Specifications
Safety standards IEC 60950, EN 60950 (output SELV),
UL 60950, UL 508, EN 50178,
EN 60204, EN 61558-2-8.
- NEC class 2 (TCL 60 models only)
Safety approvals (TCL 24 models pending) UL/cUL 60950 recognized, File E181381
UL 508C listed, File E210002
CB-Report per IEC 60950
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2
Safety class degree of protection class 1
Case protection IP 20 (IEC 60529)
Enclosure material plastic FR2010-110C (UL 94V-0 rated)
Mounting 35 mm DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
Adapter for Wall-/Chassi Mounting (included)
Options output characteristic optimized for battery
charging available on request
Industrial Power Supplies
TCL Series 24–120 Watt
TCL–REM240 Redundancy Module
This module enables redundant operation of any two TCL models by decoupling
the 2 power supplies. It can also be used to separate sensitive loads from the main
power source.
Order code Inputs
Vin
Max power
per input
Output voltage Output current
max.
Connection
TCL–REM240
2 x 5...60 VDC 144 W Vin – 0.9 VDC
8 A
detachable screw
terminal block
Models
Specifications
Operating temperature – 10°C...+70°C max. (14°F...+158°F)
derating above 40°C (104°F): 1.5%/K
Electromagnetic compatibility in correspondence to connected units
(no internal switching device)
Dimensions same as model TCL 24 (see page 4)