Datasheet
http://www.tracopower.com Page 3 of 7
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
TSPC-240UPS Series
General Specifications (continued)
Battery charging current 0.8 – 1.2 A
Nominal battery voltage (at 25ºC) 13.6 VDC (factory setting)
Battery voltage adjustment range 13.0 – 14.4 VDC
Battery restistance test 100mOhm min. (normal mode at 25ºC)
Battery test current 2.5A / 60ms typ. (normal mode at 25ºC)
Battery test interval (acc. to jumper setting) 15s or 10min
Battery warning 10.4 – 11.4 VDC (buffer mode only)
Battery disconnection 9.3 – 10.2 VDC (buffer mode only)
Battery remote Off disconnects battery in buffer mode (see page 6 - connector)
Automatic battery temperature compensation range –15ºC – 50ºC
Altitude during operation 2000 m
Isolation according to IEC/EN 60950-1, UL 60950-1, UL 508
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1, CSA 22.2 No 60950-1-07
– Industrial control equipment UL 508,
CSA-C22.2 No.107
– Electrical equipment for machines EN 60204-1
– Electronic equipment for power installation EN 50178
– Safety of transformers EN 61558-2-6, EN 61558-2-16
– Control equipment for hazardous location EN 60 079-15 II3G EX nA IIC T4
– ATEX (for IP 54 enclosure) certificate no. EPS 10 ATEX 1 269 X
– Certification documents www.tracopower.com/overview/tspc-ups
Class of protection safety class I (IEC 536)
Degree of protection IP 20 (IEC/EN 60529)
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Electrostatic discharge (ESD) IEC/EN 61000-4-2 4 kV / 8 kV criteria B
– Radiated RF field immunity IEC/EN 61000-4-3 10 V / m criteria A
– Electrical fast transient / burst immunity IEC/EN 61000-4-4 2 kV criteria B
– Surge immunity IEC/EN 61000-4-5 1 kV / 2 kV criteria B
– Immunity to conducted RF disturbances IEC/EN 61000-4-6 10 V criteria A
– Power frequency field immunity IEC/EN 61000-4-8 30 A / m criteria A
– Mains voltage dips and interruptions IEC/EN 61000-4-11 criteria A
Environment – Vibration acc. IEC 60068-2-6; 3 axis, sine sweep, 10 – 55 Hz, 1 g, 1 oct/min
– Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 11 ms
Enclosure material aluminium (chassis) / stainless steel (cover)
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
Environmental compliance – Reach www.tracopower.com/overview/tspc-ups
– RoHS RoHS directive 2011/65/EU
Connection – Input output battery screw terminal (plug included)
– Signal & control detachable screw terminals (plugs included)