Datasheet

http://www.tracopower.com Page 1 of 7
UPS Uninterruptable AC/DC Power Supply TSPC-240UPS Series
Compact universal power supply for
uniterruptable 24 VDC output voltage
Battery protection for over voltage,
deep discharge, short circuit and
reverse connection
Alarm outputs for input, output and
battery condition
Remote On/Off for UPS function and
power supply
Controlled end of charge voltage by
battery temperature sensor
International safety approval package
Suitable for various external 12 VDC
lead acid batteries
* Maximum current at nominal Vout
This power supply provides an integrated professional battery management system
to charge and monitor an external lead-acid battery. The result is a complete DC-
UPS system in a compact housing with no additional parts needed. The external
connected 12 V battery will be charged and held in charged mode by the power
supply. In the event of a mains power failure the battery will supply the output po-
wer until the battery is discharged. To avoid overcharging the battery, an external
temperature sensor adjusts the battery voltage automatically to the required end
of charge voltage. This can extend the battery life. The battery is protected against
deep discharge. Mains power and battery status are monitored regularly and failu-
res indicated by corresponding LED’s and alarm outputs. The module also provides
an external On/Off input to switch-off both, power supply and battery.
Order code Input voltage range
Output current
max.*
Output Power
max.
Back up battery
TSPC 240-124 UPS
Low Line : 85 – 132 VAC
High Line: 187 – 264 VAC
24 VDC / 12 A
240 W
12V lead acid battery (to purchase on local
market, no TRACO POWER stocking item)
Models
CB
Scheme
NKAA
EMC
LVD
IEC 60950-1 UL 60950-1 UL 508 ATEX II3GEN 60950-1
EN 61558
EN 60204
TSP-TS battery temperature sensor
(10 kOhm NTC with 2m cable) optional