3. Battery
When the input DC voltage is present, the TSP-BCMU360 unit will automatically charge the connected battery to a set end of battery
charge voltage level, factory set for 25ºC for lead-acid batteries, using a constant current charging method of 1A (typical). As the bat-
tery voltage approaches the end of battery charge voltage level, the current will decrease proportionality; this characteristic is shown in
Figure 1. The user can adjust the set end of battery charge voltage level by means of the “Battery Voltage Adjust” potentiometer.
Note: For Cycle Use (repeated charging and discharging of battery), it is recommended to use a charge current of 0.4CA or smal-
ler, therefore batteries with a capacity of 2.5Ah or less should not be used with this module.
The module also provides an input connector for a temperature compensation probe. If this probe is connected, the unit will automati-
cally compensate the end of battery charge voltage level depending on the measured temperature. The connection of the temperature
probe also negates the need to change the potentiometer to compensate for a new temperature. The battery end voltage compensation
curve is shown in Figure 2. (Applicable to factory setting of 13.6V/ 25ºC)
3.1 Battery Protection
The TSP-BCMU360 module protects the connected battery against short circuit and overload by the means of a built in 40A fuse. This
fuse is a standard 40A blade type fuse, which is accessible from the front panel of the unit for ease of replacement should the fuse be
damaged during operation. The module also prevents deep discharge of the battery by disconnecting the battery from the load once
the voltage level of battery has dropped below a defined threshold. An early warning of this disconnection is given to the user by me-
ans of the BATT-OK signal (see chapter 6). The BATT-OK signal will switch off when the battery voltage is roughly 1V above the deep
discharge threshold.
Function Specification (continued)
13
.6V
1A
Figure 1 – Battery Charge Characteristics
Figure 2
13.0
13.2
13.4
13.6
13.8
14.0
14.2
14.4
14.6
14.8
15.0
-15-10 -5 0510 15 20 25 30 35 40 45 50
[V]
[ºC]
Battery End of Charge Voltage with Temperature Sensor
End of Charge Voltage
Battery Controller Module
TSP-BCMU360 Series 360 Watt