Datasheet

http://www.tracopower.com Page 2 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Input Specifications
Input voltage range TSP 070/090 85 – 264 VAC universal input
other models: 85 – 132 / 187 – 264 VAC autoselect
output current derating at operation below 100 VAC see graph B, page 4
Input voltage frequency 47 – 63 Hz
Harmonic limits EN 61000-3-2, Class A (for limited output power)
Holdup time 230 VAC 20 ms
115 VAC 10 ms at full load, 20 ms at 66% load
Inrush current 115 VAC 230 VAC
TSP 070/090 < 12 A < 20 A
TSP 140/180 < 13 A < 25 A
TSP 360 < 16 A < 25 A
TSP 600 < 25 A < 30 A
Recommended circuit breaker, TSP 070/090/140/180 6.0 – 16.0 A
characteristic B TSP 360 10.0 16.0 A
TSP 600 16.0 – 25.0 A
Efficiency 87 % typ.
Output Specifications
Output voltage adj. range 12 VDC models: 12 – 14 VDC
24 VDC models: 24 – 28 VDC
36 VDC model: 36 – 42 VDC
48 VDC models: 48 – 56 VDC
At output voltage higher than nominal output voltage
max. output current has to be reduced accordingly, in
order not to exceed max. output power.
Regulation – Input variation 0.5 % max.
– Load variation (10–100 %) 0.5 % max.
Ripple and Noise (20MHz bandwidth) 100 mV pk-pk typ. (200 mV pk-pk max. at Imax)
Electronic short circuit protection current limitation at Imax.
constant current, automatic recovery
Output overvoltage protection 12 VDC models: 20 V
24 VDC models: 35 V
36 VDC model: 43 V
48 VDC models: 60 V
Overload protection electronic overload protection
Overtemperature protection switch off at overtemperature, automatic restart
Power back immunity 12 VDC models: 16 V
24 VDC models: 35 V
36 VDC model: 48 V
48 VDC models: 63 V
Status indicator dual color LED (green: DC ok, red: DC off)
Power OK signal – trigger threshold: 12 VDC models: 9 – 11 V
24 VDC models: 18 – 22 V
36 VDC model: 27 – 34 V
48 VDC models: 36 – 46 V
– active output signal: 12 VDC models: 11.0 V ±1.0 V
(reference to –Vout) (20 mA max. for TSP 070, 40 mA max. for TSP 140)
24 VDC models: 22.0 V ±2.0V / 20 mA max.
(10 mA max. for TSP 090, 20mA max. for others)
36 VDC model: 34.0 V ±2.0 V / 20 mA max.
48 VDC models: 44.0 V ±4.0 V / 15 mA max.
– relay output DC OK = contact closed
rated: 30 VDC/1.0 A for 12/24 VDC models
rated: 30 VDC/2.0 A for 36 VDC model
rated: 48 VDC/0.5 A for 48 VDC models