Datasheet

Industrial Power Supplies
TSP-Series
http://www.tracopower.com Page 1 of 9
The TSP series comprises high performance DIN-rail mount power supplies designed
for reliable operation under difficult factory floor conditions. High immunity against
electrical disturbances and rugged metal casing make these modules the best choice
to power sensitive loads in industrial process control systems, machine tools or other
demanding industrial applications. They provide a DC-OK signal and external shut
down function. Detachable screw terminal blocks make the connection easy.
This power supply line is accompanied by a wide range of function modules for
reliable system solutions:
Redundancy modules for true current sharing in parallel operation and for
redundant systems.
Battery controller modules to configure high reliable UPS systems for 12, 24 and
48 VDC. Selection of battery packs available.
Buffer modules for protection against short time AC power loss. Maintenance
free! No batteries required.
Innovative and Powerful Features!
Rugged metal case for
harsh industrial environments
Shock and vibration proof
Worlwide Safety approval package.
ATEX certification tested in accordance
to IECEX (opt. EX)
Model TSP 090-124N meets NEC class 2
Industrial operating temperature range:
25°C to +70°C
Adjustable output voltage
Protection against short-circuit,
overvoltage and over-temperature
Power OK signal, Remote On/Off
Wall mounting (opt.)
3-year product warranty
IEC 60950-1 UL 60950-1
UL 508
UL 60079-15
ATEX II3G
Order Code Output Power
(Pmax)
**Output Voltage
(Vnom)
***Output Current
(Imax)
TSP 070–112*
72 W 12 VDC 6.0 A
TSP 090–124*
90 W 24 VDC 3.75 A
TSP 090–124N
90 W 24 VDC 3.75 A
TSP 090–148*
96 W 48 VDC 2.0 A
TSP 140–112*
144 W 12 VDC 12.0 A
TSP 180–124*
180 W 24 VDC 7.5 A
TSP 180–148*
192 W 48 VDC 4.0 A
TSP 360–124*
24 VDC 15.0 A
TSP 360–148*
360 W
48 VDC 7.5 A
TSP 600–124*
24 VDC 25.0 A
TSP 600–136
600 W 36 VDC 16.5 A
TSP 600–148*
48 VDC 12.5 A
Models
* For ATEX compliant models add appendix -EX to order code.
** Output voltage adjustable 1214 VDC, 2428 VDC and 48–56VDC
*** Max. current at nominal output voltage and operating temperature up to +40°C max.
EMC
LVD
CB
Scheme
Function Modules (see page 5)