Datasheet

Input Voltage
- AC Range
85 - 264 VAC (Full Range)
- DC Range
120 - 370 VDC (designed for, no certification)
Input Frequency
47 – 63 Hz
Input Current
- Full Load & Vin = 230 VAC
950 mA max.
- Full Load & Vin = 115 VAC
1650 mA max.
Power Consumption
- at no Load
150 mW max. (Ready to meet ErP directive)
Input Inrush Current
- at 230 VAC
60 A max.
Input Protection
T 3.15 A / 250 VAC (Internal Fuse in L & N)
Output Voltage Adjustment
±10% (by trim potentiometer)
Voltage Set Accuracy
±1% max.
Regulation
- Input Variation (Vmin - Vmax)
0.2% max.
- Load Variation (0 - 100%)
0.5% max.
0.7% max. (5 VDC model)
Ripple and Noise
(20 MHz Bandwidth)
5 VDC model:
75 mVp-p typ. (with 10 µF X7R)
12 VDC model:
75 mVp-p typ. (with 10 µF X7R)
24 VDC model:
75 mVp-p typ. (with 1 µF X7R)
48 VDC model:
150 mVp-p typ. (with 0.1 µF X7R)
Capacitive Load
5 VDC model:
20'000 µF max.
12 VDC model:
4'520 µF max.
24 VDC model:
1'130 µF max.
48 VDC model:
285 µF max.
Minimum Load
not required
Temperature Coefficient
±0.02 %/K
Hold-up Time
- at 115 VAC
16 ms min.
Start-up Time
- at 230 VAC
1'000 ms max.
Output Current Limitation
120 - 160% of Iout max.
Short Circuit Protection
Continuous, automatic recovery
Overvoltage Protection
125 - 140% of Vout nom.
Transient Response
- Response Deviation
3% max. (50% to 75% Load Step)
- Response Time
600 µs typ. (50% to 75% Load Step)
Safety Standards
- Medical Equipment
EN 60601-1
IEC 60601-1
ANSI/AAMI ES 60601-1
2 x MOPP (Means Of Patient Protection)
- Certification Documents
www.tracopower.com/overview/tpp65a
Protection Class
Class I Prepared: Connection to PE
Class II Prepared: Reinforced Insulation
Pollution Degree
PD 2: Office or Laboratory Environments
Over Voltage Category
OVC II
Input Specifications
Output Specifications
Safety Specifications
TPP 65A Series, 65 Watt
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
March 18, 2019
Page 2 / 4