Datasheet

Safety Standards
- Medical Equipment
EN 60601-1
IEC 60601-1
ANSI/AAMI ES 60601-1
2 x MOPP (Means Of Patient Protection)
- Certification Documents
www.tracopower.com/overview/tpp65
Protection Class
Class I Prepared: Connection to PE
Class II Prepared: Reinforced Insulation
Pollution Degree
PD 2: Office or Laboratory Environments
Over Voltage Category
OVC II
EMC Emission
EN 60601-1-2 edition 4 (Medical Devices)
- Conducted Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 18, class B
- Radiated Emissions
EN 55011 class B (internal filter)
EN 55032 class B (internal filter)
FCC Part 18, class B
- Harmonic Current Emissions
EN 61000-3-2, class A
- Voltage Fluctuations & Flicker
EN 61000-3-3
EMC Immunity
EN 60601-1-2 edition 4 (Medical Devices)
- Electrostatic Discharge
Air:
EN 61000-4-2, ±15 kV, perf. criteria A
Contact:
EN 61000-4-2, ±8 kV, perf. criteria A
- RF Electromagnetic Field
EN 61000-4-3, 20 V/m, perf. criteria A
- EFT (Burst)
EN 61000-4-4, ±2 kV, perf. criteria A
- Surge
L to L:
EN 61000-4-5, ±1 kV, perf. criteria A
- Conducted RF Disturbances
EN 61000-4-6, 20 Vrms, perf. criteria A
- PF Magnetic Field
EN 61000-4-8, 30 A/m, perf. criteria A
- Voltage Dips & Interruptions
230 VAC / 50 Hz:
EN 61000-4-11
30%, perf. criteria A, 25 periods
>95%, perf. criteria A, 0.5 periods
>95%, perf. criteria A, 1 period
>95%, perf. criteria B, 250 periods
115 VAC / 60 Hz:
EN 61000-4-11
30%, 25 periods, perf. criteria A
>95%, 0.5 periods, perf. criteria A
>95%, 1 period, perf. criteria A
>95%, 250 periods, perf. criteria B
Relative Humidity
95% max. (non condensing)
Temperature Ranges
- Operating Temperature
-40°C to +85°C
- Storage Temperature
-40°C to +85°C
Power Derating
- High Temperature
see application note
www.tracopower.com/overview/tpp65
- Low Input Voltage
4 %/V below 90V
Cooling system
Natural convection (no internal fan, 20 LFM)
Altitude during Operation
5000 m max.
Switching Frequency
50 - 140 kHz (PWM) (Output 1)
750 kHz typ. (PWM) (Output 2)
510 kHz typ. (PWM) (Output 3)
Insulation System
Reinfoced Insulation
Working Voltage (rated)
258 VAC
Safety Specifications
EMC Specifications
General Specifications
TPP 65 Series, 65 Watt
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
www.tracopower.com
March 19, 2019