Product Manual
HORIZONTAL -- AIR DISCHARGE MOUNTING
SHOWN IN: FIGURE 5 & 6
Swivel hanger brackets may be used to suspend unit
heaters from either the wall (figure 5) or the ceiling
(figure 6). Attach hanger base “A” to top of heater with
the four 5/16 X 18 caps screws and lockwashers (pro-
vided in envelope).
Attach main hanger frame “B” to wall or ceiling in
desired location using lag screws “C” or other suitable
attachments (supplied by others).
Lift heater into position inserting stud “D” through hole
in main hanger frame and attach lock nut “provided in
envelope) “E” tightening to within two turns of being
tight.
Swivel heater to desired position, tighten lock nut.
5
VERTICAL -- AIR DISCHARGE MOUNTING
SHOWN IN: FIGURE 7
Attach short angle brackets “A” to back of heater with
four 5/16 X 18 capscrews “B”, lockwashers “F”. Be sure
vertical leg of angle brackets face top and bottom of
heater.
Attach inverted U frames “D” to short angle brackets
with four 5/16 X 18 capscrews “K”, washers “L”,
lockwashers “M” and nuts “N”.
Attach long angle brackets “J” to inverted frames “D”
with four 5/16 X 18 capscrews “K”, washers “L”,
lockwashers “M” and nuts “N”.
Attach heater and bracket assembly to ceiling in
desired location using customer supplied equipment
sufficient to support the assembly.
INSTALLATION INSTRUCTIONS
TASKMASTER -- 5100 SERIES UNIT HEATER (part 2)
Figure 5
WALL MOUNT
HORIZONTAL DISCHARGE
Figure 6
CEILING MOUNT
HORIZONTAL DISCHARGE
Figure 7
CEILING MOUNT
VERTICAL DISCHARGE
NOTE: When mounting heater using 5/16” all thread
rod (by others) do not screw the rod more than 1/2”
beyond the inside of the case.