Product Manual
SERIES 5100
TASKMASTER
INSTALLATION INSTRUCTIONS
NOTE: Before installing disconnect switch, check heater data label
to ensure that heater electrical rating does not exceed the switch
electrical rating.
NOTE: All wiring must be done in accordance with National and
Local Electrical Codes. Supply conductors to unit must be copper.
1.) Disconnect heater from power supply.
2.) Locate and remove large knockout and two adjacent small
knockouts from heater where switch is to be mounted.
A.) 3-5KW - 1/2” diameter knockout is located centered on heater
back approximately 3 1/2” from bottom of the unit, with the two
slotted knockouts on each side.
B.) 7-50KW - 1/2” diameter knockout is located on left hand
side of heater front approximately 2 1/2” from bottom of
unit, with the two 3/16” slotted knockouts on each side.
3.) Remove the knob and mounting plate from switch assembly.
Remove terminal shield.
(NOTE: Terminal shield must be installed on disconnect switch
after incoming supply wiring has been connected).
4.) Connect the incoming power supply leads to terminals
L1-L2-L3 of the disconnect switch. Connect the incoming
ground lead to the grounding screw (or lug). On some models
with adequate access the switch may be mounted (Step 5)
prior to connecting the supply wiring.
5.) Place the switch inside the heater control compartment with
the shaft extending through the 1/2” diameter knockout. The
switch must be oriented so the terminal shield is positioned
toward the left side of the heater. Data and caution labels
must be plainly visible from open end of compartment. Align
switch assembly and mounting plate with the 3/16” slotted
knockouts in unit and secure with the #6 or #8 screws
provided.
6.) Connect the leadwires on the switch, marked T1-T2-T3 to the
heater power terminal block marked L1-L2-L3 (Note: For single
phase units remove center leadwire marked T2).
7.) Attach the “On-Off” cover to the mounting plate. Install knob
and tighten screw.
8.) Check all connectors for tightness and electrical clearances.
Close cover and latch, then restore electrical power and check
heater in each mode of operation.
DCS403, DCS603, DCS1003
POWER DISCONNECT SWITCH TASK MASTER SERIES
RATING DCS403 3 POLE 40 AMPS 600 VAC RESISTIVE
DCS603 3 POLE 60 AMPS 600 VAC RESISTIVE
DCS1003 3 POLE 100 AMPS 600 VAC RESISTIVE
January 1990
WARNING: Open supply circuit disconnect switch
before servicing unit. Failure to do so may result in
personal injury or death from electrical shock.
FORM: 8947
ECO 1-5148