Product Manual

5 OF 14
OIPM P/N 8997
FES – SERIES ASSEMBLY
Tools Required: (2) 7/16” socket or box wrenches.
To position the handle at operating height:
Step 1:
Remove and keep the hardware securing the
handle to the legs.
Step 2:
Raise handle until holes align with the upper
holes in the legs.
Step 3:
Re-insert hardware as shown, and fasten securely
.
WIRING
THE PROPER SIZE SO- type feeder cable MUST BE USED for the electrical hook-up of this heater. The proper cable size is shown in
the tables below (A.W.G./ # of conductors.) Table 1 is for cable 50ft. in length or less. Table 2 is for cable longer than 50ft.
A 25ft. cable kit can be purchased from the
factory. Refer to the kit part numbers in table at
right.
CABLE KITS INCLUDE:
25 feet of Type SO cable, with either
3-conductors or 4-conductors, depending
on the heater requirements.
To order cable kits
Phone: 1-800-495-4525
BOLTS
WASHERS
WASHERS
NUTS
Model
Table 1
Unit Rating
Cable Size - Under
50ft. long
Cable
Kit Number
FES1520-3A 15kW, 208 Volt, 3-Ph 6/4 03164001
FES1524-1A 15kW, 240 Volt, 1-Ph 4/3 08805300
FES1524-3E 15kW, 240 Volt, 3-Ph 6/4 03164001
FES1548-3E 15kW, 480 Volt, 3-Ph 12/4 03164201
FES1560-3A 15kW, 600 Volt, 3-Ph 12/4 03164201
FES3048-3A 30kW, 480 Volt, 3-Ph 6/4 03164001
FES3060-3A 30kW, 600 Volt, 3-Ph 6/4 03164001
Model
Table 2
Unit Rating
Cable Size - Over
50ft. long
Max. Cable
Length (ft)
FES1520-3A 15kW, 208 Volt, 3-Ph 4/4 120
FES1524-1A 15kW, 240 Volt, 1-Ph 2/3 215
FES1524-3E 15kW, 240 Volt, 3-Ph 6/4 150
FES1548-3E 15kW, 480 Volt, 3-Ph 12/4 140
FES1560-3A 15kW, 600 Volt, 3-Ph 12/4 190
FES3048-3A 30kW, 480 Volt, 3-Ph 6/4 300
FES3060-3A 30kW, 600 Volt, 3-Ph 6/4 350
• Feeder cable or cable kit assembly MUST BE made by
licensed electricians ONLY.
• Service panel or receptacle used to supply power to
these heaters MUST have a ground bus or ground pole
that is securely bonded to earth ground.
• Connect green ground conductor on feeder cable or
cable kit to grounding lug on heaters.
• Comply with ALL local electrical codes and the National
Electric Code (NFPA70) when providing electrical
power to these heaters.
ELECTRICAL SHOCK HAZARD
FIRE HAZARD
RISQUE DE CHOC ÉLECTRIQUE
RISQUE D’INCENDIE
Serious injury or death may occur
Blessures graves ou la mort peuvent survenir.
Disconnect from electrical supply before installing
feeder cable to these heaters.
Couper l’alimentation électrique avant d’installer un
câble
d’alimentation de ces appareils de chauffage.
Read and follow all safety information in box to
the left.
Lire et suivre toutes les consignes de sécurité dans la boîte
vers la gauche.