Product Manual
5 OF 14
OIPM P/N 8997
FES – SERIES ASSEMBLY
Tools Required: (2) 7/16” socket or box wrenches.
To position the handle at operating height:
Step 1:
Remove and keep the hardware securing the
handle to the legs.
Step 2:
Raise handle until holes align with the upper
holes in the legs.
Step 3:
Re-insert hardware as shown, and fasten securely
.
WIRING
THE PROPER SIZE SO- type feeder cable MUST BE USED for the electrical hook-up of this heater. The proper cable size is shown in
the tables below (A.W.G./ # of conductors.) Table 1 is for cable 50ft. in length or less. Table 2 is for cable longer than 50ft.
A 25ft. cable kit can be purchased from the
factory. Refer to the kit part numbers in table at
right.
CABLE KITS INCLUDE:
• 25 feet of Type SO cable, with either
3-conductors or 4-conductors, depending
on the heater requirements.
To order cable kits
Phone: 1-800-495-4525
BOLTS
WASHERS
WASHERS
NUTS
Model
Table 1
Unit Rating
Cable Size - Under
50ft. long
Cable
Kit Number
FES1520-3A 15kW, 208 Volt, 3-Ph 6/4 03164001
FES1524-1A 15kW, 240 Volt, 1-Ph 4/3 08805300
FES1524-3E 15kW, 240 Volt, 3-Ph 6/4 03164001
FES1548-3E 15kW, 480 Volt, 3-Ph 12/4 03164201
FES1560-3A 15kW, 600 Volt, 3-Ph 12/4 03164201
FES3048-3A 30kW, 480 Volt, 3-Ph 6/4 03164001
FES3060-3A 30kW, 600 Volt, 3-Ph 6/4 03164001
Model
Table 2
Unit Rating
Cable Size - Over
50ft. long
Max. Cable
Length (ft)
FES1520-3A 15kW, 208 Volt, 3-Ph 4/4 120
FES1524-1A 15kW, 240 Volt, 1-Ph 2/3 215
FES1524-3E 15kW, 240 Volt, 3-Ph 6/4 150
FES1548-3E 15kW, 480 Volt, 3-Ph 12/4 140
FES1560-3A 15kW, 600 Volt, 3-Ph 12/4 190
FES3048-3A 30kW, 480 Volt, 3-Ph 6/4 300
FES3060-3A 30kW, 600 Volt, 3-Ph 6/4 350
• Feeder cable or cable kit assembly MUST BE made by
licensed electricians ONLY.
• Service panel or receptacle used to supply power to
these heaters MUST have a ground bus or ground pole
that is securely bonded to earth ground.
• Connect green ground conductor on feeder cable or
cable kit to grounding lug on heaters.
• Comply with ALL local electrical codes and the National
Electric Code (NFPA70) when providing electrical
power to these heaters.
ELECTRICAL SHOCK HAZARD
FIRE HAZARD
RISQUE DE CHOC ÉLECTRIQUE
RISQUE D’INCENDIE
• Serious injury or death may occur
Blessures graves ou la mort peuvent survenir.
• Disconnect from electrical supply before installing
feeder cable to these heaters.
• Couper l’alimentation électrique avant d’installer un
câble
d’alimentation de ces appareils de chauffage.
• Read and follow all safety information in box to
the left.
Lire et suivre toutes les consignes de sécurité dans la boîte
vers la gauche.