Item Brochure
18
5100 Series 60 KW - 100 KW Suspended Fan Forced Unit Heater
Mounting Brackets and Accessories
5100 SD Features
Features & Specications
Dimensions (Inches)
WT.
(LBS)
KW H W D
60-70 35
1
⁄2 30
1
⁄2 14
1
⁄2 141
80-100 39
1
⁄2 37
5
⁄8 18
1
⁄2 202
5100 Series Horizontal or Vertical Mounted Fan Forced Unit Heater
CONSTRUCTION:
Heavy gauge steel cabinet with powder coated nish and control compartment housing a master terminal board. The control compartment
allows for access through a hinged and latched door, simplifying wiring, installation, and maintenance. Made in U.S.A
HEATING ELEMENT:
The heating element is a copper clad steel sheath element with continuously brazed steel ns formed to allow side draw through air ow.
OVERHEAT PROTECTION:
All units come equipped with manual reset type limit controls to de-energize the heater should an over-temperature situation occur.
FAN & MOTOR:
Single speed, single phase permanently lubricated, thermally protected motors with ball bearings. The fan override purges the unit of residual
heat at shutdown.
FIELD INSTALLED OPTIONS:
Summer fan switch to operate the fan only, and a heat stratication thermostat for high bay areas.
HEATER STAGING:
60 KW and 70 KW are three stage; 80 KW, 90 KW, & 100 KW are four stage.
SC5100 FACTORY INSTALLED ELECTRONIC STEP CONTROLLER:
The optional factory installed step controller is a rst on last off sequencer that will cycle the unit heater stages through an optional wall
thermostat. Additionally, the step controller can be controlled by any building management system with 4 to 20 MA or 0 - 10 VDC eld
supplied control signal.
Available With Setback On Demand (SD) Thermostat Factory Installed
WARNING: This product can expose you
to chemicals including nickel which is known
to the State of California to cause cancer,
and chromium, which is known to the State
of California to cause birth defects and/or
reproductive harm. For more information go
to www.P65Warnings.ca.gov.
!
WARNING: This product can expose you
to chemicals including nickel which is known
to the State of California to cause cancer,
and chromium, which is known to the State
of California to cause birth defects and/or
reproductive harm. For more information go
to www.P65Warnings.ca.gov.
!
• 24-Volt Control
• Factory pre-programmed - just set your setback temperature in the eld
• Setback feature allows up to 12 degree setback with easy-to-use adjustable slide switch
• Occupancy sensor defaults to economy mode after one hour, sensor has a 94 degree angular
range and a 16’ linear range.
• Temperature range of 50-90 degrees
• Up to two stage operation on 5103-5150 Series and up to four stages on 5160-51100 Series
• 65-second delay between stages
• Add “SD” as sufx to heater model number for factory built in option - add $437 to list
Mounting Brackets
MFG
CATALOG
NUMBER
MFG
MODEL
NUMBER
KW DESCRIPTION
LIST
07220002 A5175 60 To 70
Wall/Ceiling
Bracket
234
07220102 A51100 80 to 100
249
07220302 B5175 60 to 70
Heater
Bracket
103
07220402 B51100 80 to 100
126
07220202 V51100 60 to 100
Vertical
Bracket
386
07220502 DS5175 60 to 70
Dust
Shield
62
07220602 DS51100 80 to 100
70
07220902 OFG 5175 60 to 70
Fan
Guard
96
07221002 OFG 51100 80 to 100
120