Model
Heat
Output
Kw
Norm. CFM
Output
Fan Speed
RPM
BTUH
(1,000’s)
Volts/HZ
50/60
Amps
Copper Wire
Size 75°C
AWG
Maximum
Fuse Size
HI LO HI LO HI LO 1PH 3PH
6333D052033B300F 5 3 250 230 1550 1400 171/10.2 208/60
25.04Π
17.57 8/10 35/25
6333D052433B300F 5 3 250 230 1550 1400 17.1/10.2 240/60
21.83Π
15.38 10/12 30/20
6333D054834B300F 5 3 250 230 1550 1400 17.1/10.2 277-480/60
18.95ΠΠ
8.02 10/14 25/15
6333D054833B300F 5 3 250 - 1550 - 17.1/10.2 480/60 - 7.76 14 15
6333D055733B300F 5 3 250 - 1550 - 17.1/10.2 600/60 - 5.48 14 15
6346D102033B300F 10 6 500 460 1550 1400 34.1/20.5 208/60
49.98ΠΠ
35.06 6/8 70/45
6346D102433B300F 10 6 500 460 1550 1400 34.1/20.5 240/60
43.57Π
30.68 6/8 60/40
6346D104834B300F 10 6 500 460 1550 1400 34.1/20.5 277-480/60
37.70ΠΠ
15.87 6/12 50/20
6346D104833B300F 10 6 500 - 1550 - 34.1/20.5 480/60 - 15.35 12 20
6346D105733B300F 10 6 500 - 1550 - 34.1/20.5 600/60 - 12.28 12 20
STANDARD CABINET UNIT HEATER SPECIFICATIONS
ISSUE DATE 06/15/01 REV. DATE REV. NO. 00 ECO NO. 1-4635 P/N 00009979 SHT.08 OF 09
ΠComes factory wired as a 3-phase unit, can be field converted to single phase ΠΠcomes factory wired as 480V/3-phase/4-wire unit, can be field converted to 277V/single phase
T 46 D 08 24 1 2 B3 S C M F D P
A B C D E F G H I J K L M N
A) Series designation –T
B) Cabinet size – 33 = 33 in., 46 = 46 in., 66 = 66 in., or 79 = 79 in.
C) Inlet-outlet arrangement – A , B, C, or D
D) Rating in KW – 02 through 24
E) Voltage rating – 20 = 208V, 24 = 240V, 27 = 277V, 48 = 480V, or 57 = 600V
F) Phase – 1 = 1phase or 3 = 3phase
G) Number of wires in electric service – 2 = 2wires, 3 = 3wires, or 4 = 4wires
H) Control option – B1 through B8, or ST
I) Summer Fan Switch Option – S = Switch included or 0 = No switch
J) Over current Protection Option – C = Circuit breaker included or 0 = No protection
K) Motor Fusing Option – M = Motoring fuse included or 0 = No protection
L) Filter Option – F = Filter included or 0 = No filter
M) Disconnect Switch Option – D = Switch included or 0 = No switch
N) Special Paint Color Option – P = Special color or Blank = Standard
Standard Unit Heaters are 33” and 46” wide.
“CUSTOM-BUILT” CABINET UNIT HEATER