Submittal Data: TW36HQ2B4D
36,000 BTU/H (208/230V) Wall Mounted Heat Pump System
Job Name Location Date
Purchaser Engineer
Submitted To For
Unit Designation Schedule No.
GENERAL FEATURES
-Compact and Quiet Design
-High Efficiency DC Inverter Technology
-Vertical Swing Louver
-Wireless Remote with LCD Display
-XK-41 Wired Tether Controller ( Sold Separately)
-Low Ambient Cool to 0 deg F
-Blue Fin Condenser Coil
-5 year Limited Parts Warranty
-7 year Limited Compressor Warranty
Cooling
Fan Motor
Type Cross-Flow
Rated Capacity 33,600 BTU/H Output Power 70 W
Capacity Range 7,404-35,997 BTU/H FLA 0.4 A
Power Input (Max) 4,300 W
Airflow
SEER 18.0
Cooling Wet (Lo/Hi)
412/736 CFM
EER 8.2
Heating Dry (Lo/Hi)
412/736 CFM
Heating at 47° F
Rated Capacity 34,600 BTU/H Sound Pressure Level
Capacity Range 14,979-35,997 BTU/H
Cooling (Min/Max)
37/54 db(A)
Power Input (Max) 4,300 W
Heating (Min/Max)
37/54 db(A)
HSPF 9.0
COP 2.7 Dehumidification 7.40 pt/hr
Heating at 17° F
Rated Capacity 20,200 BTU/H
Compressor Type DC Inverter Driven Rotary
Operating Range
RLA 17.5 A
Cooling (Max)
115℉ (46 C)
(Min)
0℉ (-18 C) Refrigerant Type R410A
Heating (Max)
75℉ (24 C) Fan Motor Output Power 170 W
(Min)
-4℉ (-20 C) FLA 0.73 A
Gas Pipe Size (OD) 5/8-in Sound Pressure
Liquid Pipe Size (OD) 1/4-in Cooling/Heating 65/65 db(A)
Connection Method Flared
Factory Charge 91.7 oz Power Supply
Additional Charge 0.54 oz
Normal Operational Voltage
208/230 V, 1 Phase, 60 Hz
Pre-Charge Length 25-ft
Voltage Range
187 - 253 V
MAX Refrigerant Pipe Length 98-ft
MCA
24.0 A
MIN Refrigerant Pipe Length 10-ft
MOCP/Breaker Size
40 A
MAX Refrigerant Pipe Elevation 33-ft
Main Power Wire Size
8-2 AWG
Outdoor Unit Data
Indoor Unit Data
System Ratings
Refrigerant Piping Data
Electrical Data
Reference
Approval
Construction
All Rights Reserved
TOSOT Comfort 2017