Umatch Submittal
Model:
TU24HFI
U-MATCH
Job Name:
Schedule Reference: Date:
Specification are subject to change without notice.
24,000 BTUH Slim Duct Heat Pump System
Item Unit Specification
ODU Model
-
TU24H3O
IDU Model
-
TU24HFI
Cooling Capacity Btu/h 23,800
Heating Capacity (47°F) Btu/h 27,200
Heating Capacity (17°F) Btu/h 16,700
Cooling Capacity Range Btu/h 7,400-29,000
Heating Capacity Range Btu/h 8,200-32,400
Cooling Power Input (Max) W 2,500
Heating Power Input (Max) W 2,750
SEER
-
16.0
HSPF
-
10.0
EER
W/W
10.7
COP
W/W
3.4
Cooling Operation Range
ȯȭ
0~118.0 (–18.0~48.0)
Heating Operation Range
ȯȭ
0~75.0(–18.
0~24.0)
Gas Pipe Size (OD) Inch 5/8
Liquid Pipe Size (OD) Inch 3/8
Connection Method
-
Flared
Factory Charge oz 78.4
Additional Charge oz/ft 0.6
Pre-Charge Length ft. 25
MAX Refrigerant Pipe Length ft. 164
Min Refrigerant Pipe Length ft. 10
MAX Refrigerant Pipe Elevation ft. 49
Air Flow Volume (Cooling Wet)(Lo/Hi) CFM 570/820
Air Flow Volume (Heating Dry)(Lo/Hi) CFM 570/820
Sound Pressure Level (Min/Max) dB(A) 40/46
Dehumidication pt
/hr 0.9
Condensate Drain Lift (Height) in 33
Power Supply
-
208/230 V, 1 Phase, 60 Hz
Min/Max Voltage V 187 - 253
MCA/ Power Cable Size A 2.0
MOCP/Breaker Size A 15
Communication Wire Size
-
18-2 AWG / 300V THHN
Compressor Type
-
DC Inverter Driven Rotary
Compressor RLA A 18.0
Refrigerant Type
-
R410A
Fan Motor Power Output HP 1/6
Fan Motor FLA A 1.5
Sound Pressure Level(Cooling/Heating) dB(A) 57/57
Power Supply
-
208/230 V, 1 Phase,
60 Hz
Min/Max Voltage V 187 - 253
Power Supply Wire Size
-
10-3 AWG
MCA/ Power Cable Size A 24.0
MOCP/Breaker Size A 40
System Ratings
Indoor Unit Data
Outdoor Unit Data