Umatch Submittal

Model:
TU42HFI
U-MATCH
Job Name:
Schedule Reference: Date:
Specification are subject to change without notice.
42,000 BTUH Slim Duct Heat Pump System
Item Unit Specification
ODU Model
TU42H3O
IDU Model
TU42HFI
Cooling Capacity Btu/h 39,500
Heating Capacity (47°F) Btu/h 44,000
Heating Capacity (17°F) Btu/h 24,800
Cooling Capacity Range Btu/h 12,000-42,500
Heating Capacity Range Btu/h 13,000-52,500
Cooling Power Input (Max) W 4,700
Heating Power Input (Max) W 4,750
SEER
16.0
HSPF
9.0
EER
W/W
9.5
COP
W/W
3.3
Cooling Operation Range
ȯȭ
0~118.0 (–18.0~48.0)
Heating Operation Range
ȯȭ
0~75.0(–18.
0~24.0)
Gas Pipe Size (OD) Inch 5/8
Liquid Pipe Size (OD) Inch 3/8
Connection Method
Flared
Factory Charge oz 131.2
Additional Charge oz/ft 0.6
Pre-Charge Length ft. 25
MAX Refrigerant Pipe Length ft. 164
Min Refrigerant Pipe Length ft. 10
MAX Refrigerant Pipe Elevation ft. 49
Air Flow Volume (Cooling Wet)(Lo/Hi) CFM 950/1175
Air Flow Volume (Heating Dry)(Lo/Hi) CFM 950/1175
Sound Pressure Level (Min/Max) dB(A) 45/53
Dehumidicatio
n pt/hr 1.42
Condensate Drain Lift (Height) in 33
Power Supply
208/230 V, 1 Phase, 60 Hz
Min/Max Voltage V 187 - 253
MCA/ Power Cable Size A 3.0
MOCP/Breaker Size A 15
Communication Wire Size
18-2 AWG / 300V THHN
Compressor Type
DC Inverter Driven Rotary
Compressor RLA A 21.2
Refrigerant Type
R410A
Fan Motor Power Output HP 2 x 1/6
Fan Motor FLA A 2 x 2.0
Sound Pressure Level(Cooling/Heating) dB(A) 61/61
Power Supply
208/23
0 V, 1 Phase, 60 Hz
Min/Max Voltage V 187 - 253
Power Supply Wire Size
8-3 AWG
MCA/ Power Cable Size A 31.0
MOCP/Breaker Size A 50
System Ratings
Indoor Unit Data
Outdoor Unit Data