TM30H4O Submittal

OPERATIONAL PERFORMANCE SPECIFICATIONS
TM30H4O
Indoor Units
Combinations
Rated System
Capacity
Indoor
Unit A
Indoor
Unit B
Indoor
Unit C
Indoor
Unit D
(BtuH) (BtuH) (BtuH) (BtuH) (BtuH)
9+9 18,000 9,000 9,000 NA NA
9+12 21,000 9,000 12,000 NA NA
9+18 22,950 7,650 15,300 NA NA
9+24 27,780 7,380 20,400 NA NA
12+12 24,000 12,000 12,000 NA NA
12+18 25,500 10,200 15,300 NA NA
12+24 28,860 9,420 19,440 NA NA
18+18 28,360 14,180 14,180 NA NA
18+24 29,100 12,000 17,100 NA NA
9+9+9 25,500 8,500 8,500 8,500 NA
9+9+12 26,200 8,000 8,000 10,200 NA
9+9+18 29,800 7,650 7,650 14,500 NA
9+9+24 29,800 6,300 6,300 17,200 NA
9+12+12 28,200 8,200 10,000 10,000 NA
9+12+18 29,600 7,000 8,600 14,000 NA
12+12+12 28,500 9,500 9,500 9,500 NA
12+12+18 30,200 8,600 8,600 13,000 NA
9K + 9K + 9K + 9K 29,600 7,400 7,400 7,400 7,400
9K + 9K + 9K + 12K 29,700 7,100 7,100 7,100 8,400
9K + 9K + 12K + 12K 29,600 6,800 6,800 8,000 8,000
Indoor Units
Combinations
Rated System
Capacity
Indoor
Unit A
Indoor
Unit B
Indoor
Unit C
Indoor
Unit D
(BtuH) (BtuH) (BtuH) (BtuH) (BtuH)
9+9 19,000 9,500 9,500 NA NA
9+12 22,500 9,500 13,000 NA NA
9+18 25,380 8,460 16,920 NA NA
9+24 30,840 8,280 22,560 NA NA
12+12 26,000 13,000 13,000 NA NA
12+18 28,200 11,280 16,920 NA NA
12+24 29,900 9,900 20,000 NA NA
18+18 30,200 15,100 15,100 NA NA
18+24 31,800 13,300 18,500 NA NA
9+9+9 28,500 9,500 9,500 9,500 NA
9+9+12 28,800 8,800 8,800 11,200 NA
9+9+18 31,100 7,900 7,900 15,300 NA
9+9+24 31,500 6,750 6,750 18,000 NA
9+12+12 28,900 8,500 10,200 10,200 NA
9+12+18 30,700 7,200 9,000 14,500 NA
12+12+12 29,700 9,900 9,900 9,900 NA
12+12+18 31,500 9,000 9,000 13,500 NA
9K + 9K + 9K + 9K 30,800 7,700 7,700 7,700 7,700
9K + 9K + 9K + 12K 31,300 7,300 7,300 7,300 9,400
9K + 9K + 12K + 12K 31,600 6,800 6,800 9,000 9,000
Capacity data is based on the following conditions :
Cooling Nominal Test Conditions
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
COOLING CAPACITY (BTUH)
HEATING CAPACITY (BTUH)
without notice or without incurring obligations. All rights reserved.
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs
All Rights Reserved
TOSOT Comfort 2017