Instruction Manual
!   E6581301!
M-5 
13 
(Continued) 
G
Internal circuit 
error 
•Motor control CPU is defective. 
•The drive circuit board in the 
inverter was damaged. 
•Power device is defective. 
•Using braking function in not 
RV=,,,, mode 
•Contact your Toshiba distributor. 
•If the braking function is used, operate a motor in 
RV=,,,, mode 
G
Control power 
backup 
undervoltage 
error 
•The control voltage between +SU 
and CC terminals is too low. 
•Control power is not supplied 
through +SU and CC terminals. 
•The parameter H is not set 
correctly. 
•Check whether the voltage between +SU and CC 
terminals is DC20V or more. 
•Set H to 0 if a control power backup device 
is not connected to +SU and CC terminals. 
To reset the inverter that has been tripped 
because of this error, turn it off and then back on.
UQWV
Step-out (for 
PM motors 
only) 
•The motor shaft is locked. 
•One output phase is open. 
•An impact load is applied. 
•Unlock the motor shaft. 
•Check the interconnect cables between the 
inverter and the motor. 
Note: Please contact us if you find any trips other than the above. 
[Alarm] The following are messages only. No trip is developed. 
Error 
code
Problem  Possible causes  Remedies 
QHH
ST signal OFF
•ST terminal is in open-circuit.  •Check SW1 select 
•Close ST-CC circuit (Sink logic) 
•Close ST-P24/PLC circuit (Source logic) 
EQHH
Control power 
backup 
undervoltage 
•The control voltage between +SU 
and CC terminals is too low. 
•Control power is not supplied 
through +SU and CC terminals. 
•The parameter H is not set 
correctly. 
•Check whether the voltage between +SU and CC 
terminals is DC20V or more. 
•Set H to  if a control power backup device 
is not connected to +SU and CC terminals.
In the event of a EQHH error, the inverter will not 
be reset automatically even if the control voltage 
between +SU and CC terminals returns to its 
normal level. To reset the inverter, turn it off and 
then back it on. 
OQHH
Undervoltage in 
main circuit 
•The supply voltage between R, S 
and T is under voltage. 
•Trouble of rush current restraint 
circuit or DC circuit fuse. 
•Measure the main circuit supply voltage. 
If the voltage is at a normal level, the inverter 
requires repairing. 
•Contact your Toshiba distributor. 
TVT[
Retry 
•The inverter is in the process of 
retry. 
•A momentary stop occurred. 
•The inverter is normal if it restarts after several 
tens of seconds. The inverter restarts 
automatically. Be careful of the machine because 
it may suddenly restart. 
GTT
Point setting 
alarm 
•The frequency setting signals at 
points 1 and 2 are set too close to 
each other. 
•Set the frequency setting signals at points 1 and 2 
apart from each other. 
G
Key failure 
alarm 
•
The same key is input continuously 
more than 20 seconds.
•Check the operation panel.                   
ENT
Clear enabling 
indication 
•This message is displayed when 
pressing the STOP key while an 
error code is displayed. 
• Input terminal RES signal is ON 
during trip display. 
•Press the STOP key again to clear the trip. 
•Turn off the input terminal RES signal. 
GQHH
Emergency stop 
enabling 
indication 
•The operation panel is used to 
stop the operation in automatic 
control or remote control mode. 
•Press the STOP key for an emergency stop. To 
cancel the emergency stop, press any other key. 
JK/N
Setting error 
alarm 
An error code 
and data are 
displayed 
alternately twice 
each. 
•An error is found in a setting when 
data is reading or writing. 
•Check whether the setting is made correctly. 
FD
DC braking 
•DC braking in process 
•Field forcing in process 
•The message goes off in several tens of seconds 
if no problem occurs. [Note] 
FDQP
Shaft fixing in 
control 
•Motor shaft fixing control is in 
process. 
•If the message disappears by stop command 
(ST-CC open), it is normal. 
G
G
G
Panel indication 
overflow 
•The digit number of the item 
displayed, e.g., frequency, is in 
excess of the specified digit 
number. 
(Number of overflowing digits is 
indicated.) 
•For indication of frequency, set multiplying rate 
(H) lower. (Parameter setting that results in 
overflow is of course valid.) 