6.33.14  Overvoltage  limit  operation!
H
HH
H    : Overvoltage limit operation level
 For more details, refer to Section 6.14.2. 
6.33.15  Undervoltage trip!
!!
!
H
HH
H    : Undervoltage detection level 
H
HH
H    : Undervoltage trip selection 
H
HH
H    : Undervoltage (trip alarm) detection time 
• Function 
This parameter is used for selecting the control mode when an undervoltage is detected. (Invalid, while the 
inverter stops.) When selecting “tripping enabled,” you can also specify the time elapsed before the inverter 
trips. 
H=: (Disabled) ················  Inverter stops,but does not trip. (FL is not active.) 
H=: (Enabled) ················   The inverter trips WR if an undervoltage passes for the time set with H or 
over. (FL is activated.) 
Title  Function  Adjustment range  Default setting
H Undervoltage detection level  ~ %,  %: (auto mode)  
H Undervoltage trip selection  : Disabled, : Enabled  
H Undervoltage (trip alarm) detection time ~ sec.  
Note: For H, 100% corresponds to a voltage of 200V (for 200V class) or 400V (for 400V class) 
6.33.16  Regenerative power  ride-through  control  level!
!!
!
H
HH
H    : Regenerative power ride-through control level 
• Function 
This parameter is used to set the operation level of the regenerative power ride-through control and the 
deceleration stop. (Refer to Section 5.18.2.) 
Title  Function  Adjustment range  Default setting
H Regenerative power ride-through control level  ~ %  
Note1: Set this parameter at a value of H+5% or more. Or the braking time of regenerative power 
ride-though control could be extremely shorter. This setting is not necessary if H is set to  (auto 
mode). 
Note2:  When power on or reset operation, the power supply voltage is detected. If the setting value of parameter 
H is too low, the setting value is automatically adjusted to stabilize the performance. 
Note3:  For H, 100% corresponds to a voltage of 200V (for 200V class) or 400V (for 400V class) 
6.33.17  Braking  answer waiting  time!
!!
!
H
HH
H    : Braking answer waiting time 
• Function 
This parameter is used to set the waiting time for answer from system (Input terminal function setting: 
System supporting sequence (BA: Braking answer 
, 
)). After start of operation, if no answer is 
received in set time (
H
), the inverter trips (
G
). 
Title  Function  Adjustment range  Default setting
H Braking answer waiting time 
:Disabled 
~ sec. 