5. Communications-related parameters
On the network, the VF-AS1/PS1 (including the PDP002Z) serves as a slave device. Using
the parameters listed below, set the slave device on the network and its mode of operation.
The GSD files used to configure the PDP002Z can be downloaded from the following web
site.
VF-AS1 http://www.inverter.co.jp/product/inv/vfas1/pdp/
VF-PS1 http://www.inverter.co.jp/product/inv/vfps1/pdp/
Parameter Function Adjustment range Default setting
f830* Communication
option setting 1
(PPO TYPE)
0: None
1: PPO TYPE 1
2: PPO TYPE 2
3: PPO TYPE 3
4: PPO TYPE 4
0
f851 Inverter operation at
the communications
loss action
(Network wire breaks)
0: Stop and break of connection
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation frequency
set with f852)
0
f852 Preset speed operation
selection
0: None
1 to 15: Preset speed
0
f853 Monitoring of
communication
device station
address
Displays the station address assigned with the
DIP switch.
0 to 125
1
f854** Monitoring of
communications
device’s baud rate
Displays the network communication speed set
with the DIP switch.
0: 12 Mbit/s
1: 6 Mbit/s
2: 3 Mbit/s
3: 1.5 Mbit/s
4: 500 kbit/s
5: 187.5 kbit/s
6: 93.75 kbit/s
7: 45.45 kbit/s
8: 19.2 kbit/s
9: 9.6 kbit/s
255: Disabled
0
* When the parameters are changed, the power must be cycled to the VF-AS1/PS1 for the
changes to take effect.
** The baud rate of the PDP002Z is automatically set by configuration a baud rate for the
master.
*** The version described on the nameplate and the version of PDP002Z displayed by the
status monitor is different.
Ex.) When the version describe on the nameplate is “V10
1”, it displays “16.01” in the
status monitor.(In the hexadecimal number , it becomes “10.1”.)