The UPS is to be installed in a controlled environment.
Improper storage and installation environment may deteriorate insulation, shorten
component life and cause malfunctions.
Keep the installation environment per standard described as follows:
TABLE 1.1 UPS Installation Environment
No. Item Environment standard
1
Installation
location
Indoors
2 Ambient
temperature
Minimum temperature: 32 °F(0 °C), Maximum temperature: 104 °F(40 °C)
average temperature over any 24-hour period must be in the range 41 °F (5 °C)
to 95 °F(35 °C).
3 Relative humidity
The relative humidity must be held between 5
condensation due to temperature changes.
4 Altitude This equipment must not be applied at altitude that exceeds 2250m(7380ft)
above seal level.
5 Dust
atmospheric dust levels. In particular, that dust should not inclu
oils or fats, or organic materials such as silicone.
6 Inflammable gas
following
IEC654-4
Part 4
There should be no inflammable/explosive gas.
Hydrogen sulfide (H
2
S) No more than 0.003 PPM
Sulfurous acid gas (SO
2
) No more than 0.01 PPM
Chlorine gas (Cl
2
) No more than 0.002 PPM
Ammonia gas (NH
3
) No more than 1 PPM
Nitrous oxides (NO
x
) No more than 0.05 PPM
Ozone (O
3
) No more than 0.002 PPM