Instruction Manual
E6581364 
8 
2.1.1. Switching circuit connection diagram, Time chart, 
Parameter settings 
Title  Function  Adjustment range  Setting value 
Output signal selection of commercial 
power/inverter switching 
0 to 3  2 or 3 
Commercial power/inverter switching 
frequency 
0 to   Power supply frequency 
*3
Inverter side switching waiting time  0.1 to 10.0 seconds  Different for each model 
*3
Commercial power side switching waiting 
time 
0.37 to 10.0 seconds  0.62 
Commercial power switching frequency 
holding time 
0.1 to 10.0 seconds  2.0 
*1
Input terminal selection #6 (S2)  0 to 135 
20 
(Emergency stop) 
Input terminal selection #7 (S3)  0 to 135 
102 
(Commercial power run 
switching) 
Output terminal selection #1 (OUT1)  0 to 119 
46 
(Commercial power/inverter 
switching output 1) 
Output terminal selection #2 (OUT2)  0 to 119 
48 
(Commercial power/inverter 
switching output 2) 
*1:Be careful about Items 5 and 7 in 2.2, “Precautions.” 
*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of 
*3: and  are included the operation time of the relay and the magnet contactor.     
In almost all cases, it is not necessary to change these parameter settings.
Commercial power 
switching frequency 
Commercial power switching 
frequency hold time 
   
Commercial power 
run switching signal
 S3-CC
ON 
ON
ON
ON 
ON
ON
0Hz
ON
Inverter-side switching 
wait time 
*2
Frequency after speed is 
detected 
Commercial power   
switching wait time 
S
p
eed detection time
Inverter run
Commercial power run  Inverter run
Setting frequency
P24-OUT1(RY1) 
for inverter
 run 
output 
P24-OUT2(RY2)
for commercial 
power run
 output
 Run signal
  F-CC
Stand-by signal 
 ST-CC
F L 
FLA  FLC 
FLX 
S3 
MC3 
MC1 
F 
(
Inverter
)
(Commercial 
power) 
S3 
RY1(Inverter) 
RY2(Commercial 
p
ower
)
MC3 
Inverter protective 
action signal 
MC2 
MC2 