E6581364 
7 
2. Commercial Power Supply/Inverter Switching 
The motor runs on commercial power supply under rated operating conditions and when the motor 
runs in energy saving mode with its input power frequency lowered, this circuit switches the motor 
to the inverter power without stopping the motor.
2.1. Standard connection diagram 
*1: The control power supply backup option (Model: CPS002Z) is needed.
*2: Observe the Item 1 in 2.2, “Precautions.”
*3: See Item 2 in 2.2, “Precautions.” 
*4: Be careful about Items 3 in 2.2, “Precautions.” 
*5:
 Be careful about Items 5 and 7 in 2.2, “Precautions.” 
*6: Be careful about Item 6 in 2.2, “Precautions.
MC1 
*2
For motor protection 
 THR 
*4
Motor
FL
G / E
F 
RES
CC
R/L1 
S/L2 
T/L3 
U/T1
V/T2
W/T3
FLC 
FLB 
FLA 
Run 
command 
S1
ST
R 
S2
S3
OUT2 
P24/PLC 
OUT1 
RY2 
PO 
PB 
PC/-
PA/+
Main circuit 
Stand-by 
*7
Reset 
*6
Emergency 
stop 
*5
CCA
RX
VI/II 
RR/S4
PP
A
M
FM
OUT1
MCCB 
Common 
I M
RY1 
Protective action 
detection
 relay 
MC3 
*2
MC2 
*3
+SU 
Control 
circuit
Control power supply 
backup option 
*1
NO 
CC 
Commercial run 
switching signal
*7: VF-AS1's 'WP1/WN1' model and VF-PS1 don't have 'ST' 
terminal. Please set next parameter for use 'S3' terminal as 
'ST' function. 
f110 (Always ON function selection 1)    = 0 
  f115 (Input terminal function selection: S1)    = 6 