Instruction Manual
E6581364 
3 
1.1.1. Switching circuit connection diagram, Time chart, 
Parameter settings 
Title  Function  Adjustment range  Setting value 
Output signal selection of commercial 
power/inverter switching 
0 to 3 
1 (Automatic switching in case 
of trip) 
*3
Inverter side switching waiting time  0.1 to 10.0 seconds  Different for each model 
*3
Commercial power side switching waiting 
time 
0.37 to 10.0 seconds  0.62 
*1
Input terminal selection #6 (S2)  0 to 135 
20 
(Emergency stop) 
Output terminal selection #1 (OUT1)  0 to 119 
46 
(Commercial power/inverter 
switching output 1) 
Output terminal selection #2 (OUT2)  0 to 119 
48 
(Commercial power/inverter 
switching output 2) 
*1:Be careful about Items 5 and 7 in 1.3, “Precautions.” 
*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of 
*3: and  are included the operation time of the relay and the magnet contactor.     
In almost all cases, it is not necessary to change these parameter settings. 
Setting 
frequency 
Inverter-side switching wait 
time 
*2
Frequency after speed is 
detected 
Commercial power   
switching wait time 
S
p
eed detection time
Inverter run
Commercial power run 
P24-OUT1(RY1) 
for inverter
 run 
output 
P24-OUT2(RY2)
for commercial 
power run
 output
 Run signal
  F-CC
Stand-by signal 
 ST-CC
ON
ON
ON 
ON
ON
0Hz
 Reset signal
  RES-CC
Inverte
r
trip occurs 
ON 
Inverter run
Inverter  protective 
action signal
F L 
FLA  FLC 
FLX 
X 
F 
OFFON 
X 
MC3 
MC2 
RY1 
(
Inverter
)
X 
MC3 
MC1 
   MC2 
   RY2 
(Commercial 
p
ower
)
X 