Instruction Manual
E6581364 
2 
1. Commercial Power Supply Backup 
When the inverter’s protective function is activated, switching power to commercial power supply 
makes the motor run immediately.
1.1. Standard connection diagram 
*1: The control power supply backup option (Model: CPS002Z) is needed.
*2: Observe the Item 1 in 1.3, “Precautions.”
*3: See Item 2 in 1.3, “Precautions.” 
*4: Be careful about Items 3 in 1.3, “Precautions.” 
*5:
 Be careful about Items 5 and 7 in 1.3, “Precautions.” 
*6: Be careful about Item 6 in 1.3, “Precautions.
MC1 
*2
For motor protection 
 THR 
*4
Motor
FL
G / E
F 
RES
CC
R/L1 
S/L2 
T/L3 
U/T1
V/T2
W/T3
FLC 
FLB 
FLA 
Run 
command 
S1
ST
R 
S2
S3
OUT2 
P24/PLC 
OUT1 
RY2 
PO
PB 
PC/-
PA/+
Main circuit 
Stand-by 
*7
Reset 
*6
Emergency 
stop 
*5
CCA
RX
VI/II 
RR/S4
PP
A
M
FM
OUT1
MCCB 
Common 
I M
RY1 
Protective action 
detection
 relay 
MC3 
*2
MC2 
*3
+SU 
Control 
circuit
Control power supply 
backup option 
*1
NO 
CC 
*7: VF-AS1's 'WP1/WN1' model and VF-PS1 don't have 'ST' 
terminal. Please set next parameter for use 'S3' terminal as 
'ST' function. 
f110 (Always ON function selection 1)    = 0 
  f117 (Input terminal function selection: S3)    = 6 