Datasheet
TOSHIBA | 77
Cooling and heating output figures are based on calculations and "general" test data. All figures are to taken as approximations. The properties of the third party CX Coll will have an affect on the performance of the outdoor units.
All capacity data shown is based on the following Rated Conditions:-
• Cooling (Rated): Indoor air temperature 27 °C DB/19°C WB, Outdoor air temperature: 35°C DB
• Heating (Rated): Indoor air temperature 20°C DB, Outdoor air temperature: 7 °C DB/6°C WB.
Cooling Mode Coil “Air On” Temp : Minimum 15°CWB (18°CDB) / Maximum 24°CWB (32°CDB)
Air temperatures flowing across the coil below this level, can in some circumstances, cause icing and freezing issues with the coil and eventually forcing the system to shut down and also be detrimental to the outdoor unit itself.
Heating Mode Coil “Air On” Temp : Minimum 15°CDB / Maximum 28°CDB
In the reverse cycle mode when the outdoor unit is producing hot gas, the coil in the AHU is effectively the condenser. Air temperatures flowing across the coil below this level, can cause over condensing of the refrigerant.
This can result in liquid being returned to the compressor which will cause a mechanical failure of the outdoor unit. Low air temperatures will also cause the unit to use it's defrost mode more often.
Fresh Air Intake
If you wish to use Fresh Air which is outside of these Coil “Air On” limits it has to either be pre-conditioned by other equipment, or mixed with return air (or a combination of both) so that it remains inside these limits, in order to ensure reliable
operation.
Automatic Mode
Please be aware that frequent mode changes could occur when using Automatic mode.
TA sensor
The TA sensor should be positioned in the return air duct. In case, it's not representative enough of the occupants area temperature, remote temperature sensor TCB-TC21LE2 should be used in the room.
RAV- DXC010
Dimensions (HxWxD) mm 400x300x150
Weight kg 10
Operating range - Cooling coil "Air on" temp °C 15°CWB÷24°CWB
Operating range - Heating coil "Air on" temp °C 15°CDB÷28°CDB
Power supply V-ph-Hz 220/240-1-50
DX Controller unit
Physical data
AHU DX Controller
Piping
Outdoor Unit
Controller
Indoor Unit
Controller
Air Handling Unit (field supplied)
RAV- DXC010 DXC010 DXC010 DXC010 DXC010 DXC010 DXC010
Outdoor Unit Cooling Capacity 2 HP 3 HP 4 HP 5 HP 6 HP 8 HP 10 HP
DI RAV-SM564ATP-E RAV-SM804ATP-E RAV-SM1104ATP-E RAV-SM1404ATP-E RAV-SM1603AT-E RAV-SM2244AT8-E RAV-SM2804AT8-E
SDI RAV-SP564ATP-E RAV-SP804ATP-E
RAV-SP1104AT-E
RAV-SP1104AT8-E
RAV-SP1404AT-E
RAV-SP1404AT8-E RAV-SP1604AT8-E
Cooling capacity (min-rated*-max) DI kW 4,1 - 5,3 - 5,6 5,4 - 7,1 - 7,4 7,2 - 10,0 - 11,2 10,1 - 12,5 - 13,2
Cooling capacity (min-rated*-max) SDI kW 4,1 - 5,3 - 5,6 5,4 - 7,1 - 8,0 7,2 - 10,0 - 12,0 10,1 - 12,5 - 14,0
Heating capacity (min-rated*-max) DI kW 4,6 - 5,6 - 6,3 7,5 - 8,0 - 9,0 8,1 - 11,2 - 12,5 11,3 - 14,0 - 16,0
Heating capacity (min-rated*-max) SDI kW 4,6 - 5,6 - 7,4 7,5 - 8,0 - 10,6 8,1 - 11,2 - 13,0 11,3 - 14,0 - 16,5
AHU Air Volume (min-rated*-max) m
3
/h - l/s 720 - 900 - 1080 1060 - 1320 - 1580 1280 - 1600 - 1920 1680 - 2100 - 2520 1850 - 2800 - 3740 2880 - 3600 - 4320 3360 - 4200 - 5040
Coil Internal Volume (min-max) dm
3
0,8 - 1,1 1,0 - 1,4 1,5 - 2,1 1,7 - 2,7 1,7 - 3,2 3,0 - 4,2 3,0 - 5,4
DX Controller unit
Performance data
12,6 - 14,0 - 16,0
14,1 - 16,0 - 19,0
14,1 - 20,0 - 22,4
16,1 - 22,4 - 25,0
20,1 - 23,0 - 27,0
22,5 - 27,0 - 31,5
RANGE